3.4 Abnormal High Pressure (Detected by the HPS) (E3)
Error code E3
Error generation The error is generated when the high-pressure switch is activated during compressor operation.
Causes The possible causes are:
P Abnormal high pressure caused by too much refrigerant or by non-condensable gas (air or
nitrogen)
P Inaccuracy of the high-pressure switch
P Broken or disconnected high-pressure switch harness
P Malfunctioning high-pressure switch connector connection
P Malfunctioning outdoor unit PCB
P Malfunctioning refrigerant piping circuit
P Indoor unit air filter is clogged (Heat mode)
P Outdoor heat exchanger dirty (Cool mode)
P Outdoor fan malfunction (Cool mode)
P Stop valves remained close
HPS settings The table below contains the preset HPS values.
Applicable units Abnormal Reset
R(Y)P71/100/125L > 33 bar < 25.5 bar