Service manual

ESIE03–01 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–41
3
3
4
5
1
The fan is turning
clockwise
To troubleshoot, proceed as follows:
Excessive
compressor current
To troubleshoot, proceed as follows:
The fan is turning
clockwise.
Check condensator
connection.
Refer to:
fan motor
condensator connection
.
Is the
connection
correct?
Replace fan
motor.
Correct the connection.
Refer to:
fan motor
condensator connection
.
No
Yes
Is there
a suitable
power supply? (Voltage,
lack of phase, etc.)
Provide suitable
power supply.
No
Is the current higher
than the setting of the
overcurrent relay?
Replace
overcurrent
device.
Yes
Yes
No
The compressor current is
excessive.
Check power
supply
Replace
compressor.