Service manual

Error Codes: Outdoor Units ESIE03–01
3–40 Part 3 – Troubleshooting
3
1
3
4
5
The fan does not
rotate
To troubleshoot, proceed as follows:
1 Remove obstacles so the
fan rotates correctly or
replace the fan.
2 Reconnect connector.
Try to rotate the
fan with your
hand.
Can
you rotate the
fan smoothly?
No
Check capacitor
Yes
Is
the capacitor in
good condition?
Yes
1 Replace the capacitor.
2 Reconnect connector.
No
The fan does not
rotate.
Check outdoor
unit type.
Is the unit a
R(Y)P71B?
The unit is a
R(Y)P100-125B
No
Disconnect
connector X14 on
outdoor unit PCB.
Disconnect
connectors X14A
and X15A on
outdoor unit PCB.
Yes
1 Check motor windings.
2 Reconnect connector.