Service manual
Error Codes: Indoor Units ESIE03–01
3–36 Part 3 – Troubleshooting
3
1
3
4
5
2.8 Malfunctioning Remote Controller Air Thermistor (CJ)
Error code CJ
LED indications The table below shows the LED indications.
Error generation The error is generated when the remote controller thermistor becomes disconnected or shorted while
the unit is running.
Even if the remote controller thermistor is malfunctioning, the system can operate with the system
thermistor.
Causes The possible causes are:
P Malfunctioning thermistor
P Broken wire.
Troubleshooting To troubleshoot, proceed as follows:
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Operation HAP (green) HBP (green)
Normal
cc
Malfunctioning
cc
Turn the power supply
off once and then
back on
Replace remote controller.
Could be outside cause
(noise...) other than
malfunction
Is CJ
displayed on the
remote
controller?
NO
YES