1.13 Outdoor Safety Device: Thermal Protector Fan Motor
Thermal protector
fan motor
The table below describes the thermal protector of the fan motor.
Applicable
outdoor unit
Wiring
symbol
Location
safety
Settings Type
Abnormal Reset Reset
RP71L7V1
Q1M
Outdoor fan
motor
Q1M con-
nected to
X11A
Q2M con-
nected to
X12A
> 135±5°C < 95±15°C Automatic
RYP71L7V1
RP71L7W1
RYP71L7W1
RP100L7V1
RYP100L7V1
RP100L7W1
RYP100L7W1
RP125L7W1
Q1M and
Q2M