Service manual

Troubleshooting ESIE03–01
3–18 Part 3 – Troubleshooting
3
1
3
4
5
1.11 Overview of the Indoor Safety Devices
Overview The table below contains an overview of the indoor safety devices.
Applicable unit
Thermal protector fan motor
Thermal fuse fan
motor
Abnormal Reset (automatic)
FH(Y)C(P) > 130 ± 5°C < 83 ± 20°C N.A.
FHYBP N.A. N.A. > 152°C
FH(Y)(P) > 130 ± 5°C < 83 ± 20°C N.A.
FUYP > 130 ± 5°C < 83 ± 20°C N.A.
FDYP N.A. N.A. > 160°C
FAYP > 130 ± 5°C < 83 ± 20°C N.A.
FH(Y)K(P) > 120 ± 5°C < 105°C N.A.
FDYMP N.A. N.A. >152°C