Service manual
Troubleshooting ESIE03–01
3–14 Part 3 – Troubleshooting
3
1
3
4
5
P In the case of the shaded error codes, "inspection" is not displayed. The system operates, but be
sure to inspect and repair it.
Note Operation when a malfunction occurs may differ according to the model.
U4 or UF Failure of transmission (between indoor and outdoor unit) Wrong wiring between indoor and outdoor
units or malfunction of the PC board
mounted on the indoor and the outdoor
units. If UF is shown, the wiring between the
indoor and outdoor units is not properly
wired. Therefore, immediately disconnect
the power supply and correct the wiring.
(The compressor and the fan mounted on
the outdoor unit may start operation inde-
pendent of the remote controller operation.)
U5 Failure of transmission (between indoor unit and remote con-
troller)
Transmission between indoor and remote
controller is not being correctly carried out.
U8 Failure of transmission (between "main" and "sub" remote
controller
Transmission between "main" and "sub"
remote controller is not being correctly car-
ried out.
UA Failure of field setting System setting mistake for Twin system.
UC Address duplication of central remote controller
Malfunction
Code
Contents/Processing Remarks