Service manual

ESIE03–01 Overview of the heating mode functions
Part 2 – Functional Description 2–49
3
2
4
5
1
3.7 Normal Outdoor Fan Control in Heating Mode
Applicable units RYP71-125L
Purpose The purpose of the normal outdoor fan control is to:
P Reduce the chance of overload during high ambient temperature.
P Reduce the chance of icing up.
Method Normal fan control operation is done after 5 min of starting fan control operation.
The operation range is divided into three areas (A, B and C).
Example For area A, the fans go:
P From L speed to OFF at 52.3°C
P From OFF to L speed at 50.3°C.
10 17 24 30
21
9
6
4
,5
-1
-
10
A
B
56.0
62.5
OFF
L OFF
L
H
H
HH
L
55.0
54.0
53.0
52.3
50.3
47.3
AB
Outdoor air
temp. (°CDB)
Indoor air
temp.
(°CDB)
Indoor heat
exchanger
temp.