Service manual

Overview of the heating mode functions ESIE03–01
2–42 Part 2 – Functional Description
3
1
2
4
5
Defrost ending
RYP71-125L
The defrost operation ends:
P After 10 min, or
P As soon as one of the following conditions is met after 1 min or more:
- Outdoor heat exchanger temp. 10°C
- Discharge pipe temp. > 120°C.
Hot start after
defrosting
The hot start function is activated:
P 40 s after the defrosting ending, or
P When Tc > 34°C (indoor heat exchanger temperature).
Used input The defrost control uses the following inputs:
4 Hot start after defrost The unit remains in the hot start standby (indoor unit fan
OFF) mode for:
P 40 s after defrost ending, or
P Until the indoor heat exchanger temperature increases.
Note Control and time Description
Input
Connection on
indoor PCB
Connection on
outdoor PCB
Outdoor thermistor R1T
Outdoor heat exchanger thermistor R2T
Discharge pipe thermistor R3T
Defrosting start temperature changeover switch DS1-2
Defrosting forced time changeover switch DS2-1