Overview of the cooling mode functions ESIE03–01
2–38 Part 2 – Functional Description
3
1
2
4
5
2.7 Condensation Avoidance Control
Applicable units FHYP
Operating modes Regardless of whether the thermostat is ON or OFF, the condensation avoidance control can function
in the following operating modes:
P Cooling (automatic), or
P Dry keep.
Method To avoid condensation on the swing flap, the condensation avoidance control is activated:
Stage Description
1 The fan operates in cooling mode with the blade in downward position (set on the remote
controller).
2 After 30 min, the blade moves to a horizontal position.
3 After 1 h operation in horizontal position, the blade moves back to its downward position
for 30 min.
4 The unit operation is reset by:
P Changing the operating mode into “heating” or “fan”, or
P Changing the air flow direction, or
P Turning the unit operation ON or OFF.