Service manual
ESIE03–01 General Functionality
Part 2 – Functional Description 2–23
3
2
4
5
1
1.16 Overcurrent Protection Function
Purpose The purpose of the “Overcurrent Protection Function” is to protect the unit against excessive current
drains.
Method If the Current Transducer detects an overcurrent, the unit will trip on E6 error after 4 times detection.
“J2” will be displayed if the overcurrent detection sensor has a malfunction.
Unit Compressor Current (A)
RYP71L7V1 JT90FA-V1N 25.3
RYP71L7W1 JT90FA-YE 11.5
RYP100L7V1 JT125FA-V1N 38
RYP100L7W1 JT125FA-YE 11.5
RYP125L7W1 JT160FA-YE 15