SiUS181631EA Troubleshooting for Outdoor Unit
Troubleshooting 259
7.30 Transmission Error between Centralized Remote
Controller and Indoor Unit
Error Code
UE
Method of Error
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Error Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Transmission error between optional controllers for centralized control and indoor unit
Connector for setting master controller is disconnected.
Defective PCB of centralized remote controller