Troubleshooting for Outdoor Unit SiUS181631EA
258 Troubleshooting
7.29 Address Duplication of Central Remote Controller
Error Code
UC
Method of Error
Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Error Decision
Conditions
The malfunction decision is made as soon as the abnormality is detected.
Supposed
Causes
Address duplication of centralized remote controller
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Change the setting so that
the centralized address is not
be duplicated.
Replace the defective indoor
unit PCB (control PCB).
Centralized address is
duplicated?
NO
(R22106)
YES