Specifications

4P357732-1 2014.04 Page 4 of 58
1.2 Limitations
The number of control commands per indoor unit is limited to 7000 per year.
If the BMS controls the units by using an automatic control program, please make sure it doesn’t exceed
this limitation.
1.3 Specifications
Daikin equipment
connection
DIII net (F1F2)
maximum 64 indoor units (groups) and maximum 10 outdoors (addr 1-00 till 4-15)
BMS equipment protocol
Modbus RS485 (2 wire, max 500m)
Installation place
Indoor installation
Operation condition
Temp range 0 till 60°C
Dimensions
379 x 87 x 124 mm
Mass (Weight)
2,1 kg
Power supply
220 240 VAC 50 Hz
Software
The Modbus Interface DIII software can be updated with the Daikin Updater PC
software
Refer to chapter “4.2 Software update with Updater” for details
Installation manual
Provided with the option
Design guide
Latest version available on:
http://www.daikineurope.com/support-and-manuals/product-information