Specifications
4P357732-1 – 2014.04 Page 34 of 58
Input register
VRV
Sky-air
HRV
Split
VRV hydrobox
LT & HT
Air curtains
ERQ control box
Heating
Applied
Leaving water set
point
Leaving water set point cooling
and heating
* Applied: “cooling negative
leaving water set point” feature:
depending if function is integrated
in unit.
(see chapter
1.4.1 Overview of compatible
Daikin models with DIII connection
(detail))
-
-
-
-
O
-
-
O
O*
32801 (1-00)
32805 (1-01)
.. (step of 4)
33053 (4-15)
Bit
Description
Meaning
15..0
Heating
water Set
point
- 127,9 ..
127,9°C
(unity: 0,1°C)
16 bit signed integer equals the value multiplied by
10
(bit 15= sign)
32802 (1-00)
32806 (1-01)
.. (step of 4)
33054 (4-15)
15..0
Cooling
water Set
point
- 127,9 ..
127,9°C
(unity: 0,1°C)
16 bit signed integer equals the value multiplied by
10
(bit 15= sign)
Input register
VRV
Sky-air
HRV
Split
VRV hydrobox
LT & HT
Air curtains
ERQ control box
Heating
Applied
Domestic hot
water
Reheat enable/ disable status
Storage start requested
Storage set point
-
-
-
-
O
-
-
O
-
Quiet mode (low
noise)
-
-
-
-
O
-
-
O
O
32803 (1-00)
32807 (1-01)
.. (step of 4)
33055 (4-15)
Bit
Description
Meaning
15..8
Storage
set point
- 128 .. 127°C
(unity 1°C)
8 bit signed integer equals the value multiplied by 10
(bit 15= sign)
7..3
-
2
Low noise
On/Off
status
0: Off
1: On
1
Storage
started
request
0: none
1: started
request
0
Reheat
On/Off
status
0: Off
1: On