Specifications

4P357732-1 2014.04 Page 29 of 58
Input register
VRV
Sky-air
HRV
Split
VRV hydrobox
LT & HT
Air curtains
ERQ control box
Heating
Applied
Leaving water set
point range
Leaving water set point range
cooling and heating
-
-
-
-
O
-
-
O
O
31402 (1-00)
31406 (1-01)
.. (step of 4)
31654 (4-15)
Bit
Description
Meaning
15..8
Unit
cooling
water set
point
upper limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 15= sign)
7..0
Unit
cooling
water set
point lower
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 7= sign)
31403 (1-00)
31407 (1-01)
.. (step of 4)
31655 (4-15)
15..8
Unit
heating
water set
point
upper limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 15= sign)
7..0
Unit
heating
water set
point lower
limit
- 128 .. 127°C
(unity 1°C)
8 bit signed integer
(bit 7= sign)
(Note: Unit set point range is depending on unit e.g. 5 till 20°C.
In some user interfaces, it is possible to change the set point range towards the user e.g. 10 till 15°C.
But these values are independent from the unit set point range. Meaning unit set point range values are
not modified. E.g. 5 till 20°C)