Specifications

4P357732-1 2014.04 Page 27 of 58
Input register
VRV
Sky-air
HRV
Split
VRV hydrobox
LT & HT
Air curtains
ERQ control box
Heating
Applied
Indoor unit
capability
Fan speed capability(*not split)
Fan speed levels capability(*not
split)
Fan direction capability(*not split)
Fan direction levels capability(*not
split)
Dry mode capability
Auto mode capability
Heating mode capability
Cooling mode capability
Fan mode capability (*not split)
O
O
-
O*
O
O
O
O
O
31001 (1-00)
31004 (1-01)
.. (step of 3)
31190 (4-15)
Bit
Description
Meaning
15
Fan speed
capability
0:Not exist
1: Exist
14
Fan speed
steps
capability
0 till 7
This value has only meaning if “Fan speed capability”
exists
0: -, 1:Fix, 2: 2step, 3: 3 step, 4: 4 step, 5: 5 step, 6: -
, 7: -
13
12
11
Fan
direction
capability
0:Not exist
1: Exist
10
Fan
direction
steps
capability
0 till 7
This value has only meaning if “Fan direction
capability” exists
-, 7: -
9
8
7
-
6
-
5
-
4
Dry mode
capability
0:Not exist
1: Exist
3
Auto mode
capability
0:Not exist
1: Exist
2
Heating
mode
capability
0:Not exist
1: Exist
1
Cooling
mode
capability
0:Not exist
1: Exist
0
Fan mode
capability
0:Not exist
1: Exist
0: -, 1:Fix, 2: 2step, 3: 3 step, 4: 4 step, 5: 5 step, 6: -