Installation manual

English 18
8. ELECTRIC WIRING WORK
8-1 GENERAL INSTRUCTIONS
Make certain that all electric wiring work is carried out by qualified personnel according to the applicable
legislation and this installation manual, using a separate circuit. Insufficient capacity of the power supply cir-
cuit or improper electrical construction may lead to electric shocks or a fire.
Make sure to install an earth leakage breaker in accordance with applicable legislation. Failure to do so may
cause electrical shock and a fire.
Do not turn on the power supply (of the indoor unit) until all the installation work is completed.
Make sure to earth the air conditioner.
Earthing resistance should be according to applicable legislation.
Do not connect the earth wiring to gas or water piping, lightning conductor or telephone earth wiring.
Gas piping ..... Ignition or explosion may occur if the gas leaks.
Water piping ..... Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wiring......Electric potential may rise abnormally if struck by a
lightning bolt.
For electric wiring work, refer to also the “WIRING DIAGRAM” attached to the control box lid.
Never connect the power supply wiring to the terminal block for remote controller wiring, or otherwise the
entire system may be damaged.
Carry out installation and wiring of the remote controller according to the “installation manual” attached to
the remote controller.
Do not touch the Printed Circuit Board assy during the wiring work. Otherwise, it may cause damage.
8-2 SPECIFICATIONS FOR FIELD WIRING
For the wiring of outdoor units, refer to the installation manual attached to the outdoor units.
Remote controller and transmission wiring are field supply. (Refer to Table 3)
Table 3
* This will be the total extended length in the system when doing group control.
Wiring specifications are shown on the condition that the wiring has a voltage drop of 2%.
1. It shows the case when conduit piping are used. When the conduit piping are not used, use H07RN-F.
2. Sheathed vinyl cord or cable (insulation thickness: 1mm or more)
9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE
Wiring connection method
〈〈Caution for wiring〉〉
The indoor units in the same system can be connected to the power supply from one branch switch. How-
ever, selection of branch switch, branch over current circuit breaker and wiring size must be according to
applicable legislation.
For connection to the terminal block, use ring type crimp style terminals with insulation sleeve or treat the
wiring with insulation.
Wire
Size (mm
2
)
Length
Transmission wiring
H05VV-U4G
(NOTE 1)
2.5
Remote controller wiring
Vinyl cord with sheath or cable (2 wire)
(NOTE 2)
0.75 - 1.25 Max. 500m*
Insulation sleeve
Ring type crimp style terminals
Wiring
01_EN_3P249378-6L.fm Page 18 Sunday, September 30, 2012 2:30 PM