Specifications

Test Run and Operation Data ESIE02–01
4–28 Part 4 – Commissioning and Test Run
3
1
4
5
3.1 General Operation Data
During cooling
mode and dry keep
The operating conditions must be as follows:
The operation values are guidelines in the operation range:
LP: 3.0~6.5 barg (low pressure)
HP: 12.0~28.0 barg (high pressure)
Td: 60~95˚C (discharge pipe temperature compressor)
Ts: -2~15˚C (suction pipe temperature compressor)
Ti: 8~16˚C (indoor temperature difference air return – air outlet).
During heating
mode
The operating conditions must be as follows:
The operation values are guidelines in the operation range:
LP: 1.8~6.4 barg (low pressure)
HP: 13.0~28.0 barg (high pressure)
Td: 55~95˚C (discharge pipe temperature compressor)
Ts: -15~10˚C (suction pipe temperature compressor)
Ti: 12~32˚C (indoor temperature difference air return – air outlet).
Items Operating modes If the operation is out this range...
Outdoor temp.
c/o: -15 to +46˚CDB
h/p: -5 to +46˚CDB
A safety device may stop the operation.
Condensation may occur on the indoor unit and
start dripping.
Indoor temp. +14 to +28˚CWB
Indoor humidity 80%
Items Operating modes If the operation is out this range...
Outdoor temp. -10 to +15.5˚CWB A safety device may stop the operation.
Indoor temp. +15 to +27˚CDB