Field settings ESIE02–01
4–24 Part 4 – Commissioning and Test Run
3
1
4
5
2.13 DIP switch DS1
Priority The table below contains the priority of the DIP switches.
DS1-1:
E.V. opening during
defrost
The table below describes the DIP switch.
DS1-2:
Defrost starting
condition
The table below describes the DIP switch.
When... are ON Then... has priority.
■ DS1-2
■ DS2-1
DS1-2
■ DS1-1
■ DS2-2
DS1-1
Setting Illustration Function
Factory setting OFF At the start-up of the defrost operation, the E.V. will be opened to
the max. (480 pulses) for a limited time (1 or 2 min), before clos-
ing to 100 pulses.
Field setting ON The opening of the E.V. can change to the max. (480 pulses) in
order to increase the defrost capacity.
Mind the increased risk of liquid back.
12
12
Setting Illustration Function
Factory setting OFF For temperature settings at defrosting, see page 2–38.
Accumulated operation time for defrost activation = 3 h.
Field setting ON
■ Increases the temp. conditions for defrost activation with 4˚C.
■ Changes the accumulated operation time from 3 h to 40 min
in order to advance the defrosting operation.