Specifications
ESIE02–01 Field settings
Part 4 – Commissioning and Test Run 4–23
3
4
5
1
2.12 Jumpers
Input and output The table below describes the input and the output of the jumpers.
J1 The function of jumper J1 is to reduce the possibility of thermostat OFF (reduce ON/OFF cycle compr.).
J3 The function of jumper J3 is to increase the differential for thermo ON.
Item Description
Input ∆Tr Cooling ∆Tr = Tr - Ts
■ Tr = indoor unit suction air temp.
■ Ts = temp. set by the remote control
Heating ∆Tr = Ts - Tr
Output Magnetic switch compressor K1M
Factory setting (closed state) Field setting (open state)
Thermostat goes into OFF-state when
∆Tr ≤ 0.0˚C
Thermostat goes into OFF-state when
■ -0.5˚C < ∆Tr ≤ 0.0˚C for 3 min, or
■ -1.5˚C < ∆Tr ≤ -0.5˚C for 1 min, or
■ ∆Tr ≤ -1.5˚C
+1.0
0.0
∆Tr
Input: ∆Tr
Output: K1M
ON
OFF
≥ 3 min
-1.5
+1.0
0.0
-0.5
∆Tr
Input: ∆Tr
Output: K1M
ON
OFF
≥ 3 min
∆Tr
≤ 0.0˚C and ≥ 3 min
∆Tr ≤ -0.5˚C and ≥ 1 min
∆Tr
≤ -1.5˚C no delay
Factory setting (closed state) Field setting (open state)
Thermostat goes into ON-state when
∆Tr ≥ 1.0˚C
Thermostat goes into ON-state when
∆Tr ≥ 4.5˚C
+1.0
∆Tr
0.0
Input: ∆Tr
Output: K1M
ON
OFF
Pump down
+4.5
∆Tr
0.0
Input: ∆Tr
Output: K1M
ON
OFF
Pump down