Specifications

ESIE02–01 Field settings
Part 4 – Commissioning and Test Run 4–13
3
4
5
1
2.4 Overview of the Field Settings of the Indoor Units
Field settings The table below contains the possible field settings of all indoor units.
Mode
No.
First
code
No.
Description of the setting
Second code No.
01 02 03 04
10 or 20 0 Filter counter Long Short
1Filter type Long Super long External Oil mist
2 Remote thermistor of the
remote control
TH1 = rem.
control
TH1 = air
return
——
3Filter display Filter indic. No filter indic.
9 Centralized control Yes No
11 or 21 0 Number indoor to 1 outdoor Pair Twin Triple Double twin
1 Unified or indiv. set twin Group setting Indiv. setting
2Fan OFF at thermostat OFF LL-speed OFF
12 or 22 0 KRP1B51/52/53 X1/X2 output Thermostat
ON
Option Operation Malfunction
3Fan speed heating thermostat
OFF
LL-speed Set speed
5Automatic restart Disabled Enabled
13 or 23 0 Ceiling height setting Normal High Extra high
14-, 3- or 2-way air outlet 4-way 3-way 2-way
3 Horizontal discharge grill Enabled Disabled
4Air flow direction adjust range
setting
Draft preven-
tion
Standard Ceil soil pre-
vention
5Field fan speed changeover
air outlet
Standard Option 1 Option 2
6External static pressure Normal High Low
14 or 24 0 Additional timer to guard timer 0 s 5 s 10 s 15 s
15 or 25 1 Humidifier during thermostat
OFF
No Yes
3Drain pump during humidify-
ing (heating)
No Yes
5Ventilation unit indiv. setting No Yes
6Air-cleaner unit indiv. setting No Yes