Specifications
ESIE02–01 Field settings
Part 4 – Commissioning and Test Run 4–13
3
4
5
1
2.4 Overview of the Field Settings of the Indoor Units
Field settings The table below contains the possible field settings of all indoor units.
Mode
No.
First
code
No.
Description of the setting
Second code No.
01 02 03 04
10 or 20 0 Filter counter Long Short — —
1Filter type Long Super long External Oil mist
2 Remote thermistor of the
remote control
TH1 = rem.
control
TH1 = air
return
——
3Filter display Filter indic. No filter indic. — —
9 Centralized control Yes No — —
11 or 21 0 Number indoor to 1 outdoor Pair Twin Triple Double twin
1 Unified or indiv. set twin Group setting Indiv. setting — —
2Fan OFF at thermostat OFF LL-speed OFF — —
12 or 22 0 KRP1B51/52/53 X1/X2 output Thermostat
ON
Option Operation Malfunction
3Fan speed heating thermostat
OFF
LL-speed Set speed — —
5Automatic restart Disabled Enabled — —
13 or 23 0 Ceiling height setting Normal High Extra high —
14-, 3- or 2-way air outlet 4-way 3-way 2-way —
3 Horizontal discharge grill Enabled Disabled — —
4Air flow direction adjust range
setting
Draft preven-
tion
Standard Ceil soil pre-
vention
—
5Field fan speed changeover
air outlet
Standard Option 1 Option 2 —
6External static pressure Normal High Low —
14 or 24 0 Additional timer to guard timer 0 s 5 s 10 s 15 s
15 or 25 1 Humidifier during thermostat
OFF
No Yes — —
3Drain pump during humidify-
ing (heating)
No Yes — —
5Ventilation unit indiv. setting No Yes — —
6Air-cleaner unit indiv. setting No Yes — —