Specifications

SiBE18-821 Troubleshooting for Outdoor Unit
Troubleshooting 307
7.5 Malfunction of Outdoor Unit Fan Motor
Remote
Controller
Display
E7
Applicable
Models
AII outdoor unit models
Method of
Malfunction
Detection
Malfunction of fan motor system is detected according to the fan speed detected by Hall IC
when the fan motor runs.
Malfunction
Decision
Conditions
When the fan runs with speed less than a specified one for 6 seconds or more when the fan
motor running conditions are met
When malfunction is generated 4 times, the system shuts down.
Supposed
Causes
Malfunction of fan motor
The harness connector between fan motor and PCB is left in disconnected, or faulty
connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
Troubleshooting
Check No.03
Refer to P.348
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connector of
fan motor is
disconnected.
Is there any
obstacle around the
fan?
Are the
resistances
between pins above
judgment?
Can the fan
be turned smoothly
with hand after disconnect
the connector of fan
motor?
Connect the connector.
Remove the obstacle.
Replace outdoor unit PC
board.
(Q0554)
NO
NO
YES
YES
YES
Replace the fan motor of
outdoor unit.
NO
Replace the fan motor of
outdoor unit.
NO
YES
Check No.03
Check on connector of fan
motor (Refering to
information on page 348)