Specifications
SiBE18-821 Indoor Unit (SkyAir Models)
Function 107
2-2-a)-1
When a water level abnormality occurs during drain pump ON
Occurrence of drain water level abnormality
5
sec
A10
sec sec
Compressor
ON
OFF
Error processing
5min
Abnormal
Normal
Drain pan
Water level abnormality
Normal
Drain pump
ON
OFF
5min
Intermittent operation (*1)
1 The same operation as 1-2-a) "Behavior between occurrence and recovery of drain water level
abnormality" in the mode of cooling or dry.
*2
Even though the water level
abnormality could be recovered
during intermittent operation, the
operation shall be carried out
without exception.
*3
If the abnormality could not be recovered
during intermittent operation, the latter 5
min ON operation is continued until
recovery of the abnormality.
Note : ((2-2-a)-1 When a water level abnormality occurs during drain pump ON)
Recovery operation for drain water level abnormality does not activate when the water level can
be returned normal within A + 10 seconds.