Service manual
SiBE07-724_B Forced Cooling Operation Mode
Trial Operation and Field Settings 199
2. Forced Cooling Operation Mode
Outline Forced operation mode includes only forced cooling.
Detail
Indoor Unit
Outdoor Unit (RK(X)S25/35E2V1B, RK(X)S25/35G2V1B9)
Item Forced Cooling
Conditions 1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced cooling operation is allowed when the above both conditions are
met.
Start The forced cooling operation starts when any of the following conditions is
fulfilled.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor
unit for 5 seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit. (RK(X)S25/35G2V1B9 models only)
Command
frequency
RK(X)S25/35E2V1B, RK(X)S25/35G2V1B: 68 Hz
RK(X)S25/35G2V1B9: 58 Hz
End The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
Others The protection functions are prior to all others in the forced cooling operation.
ON/OFF button (SW1)
(R14086)
1
2
3
(R14085)
Screwdriver
Forced cooling
operation ON/OFF
button (SW1)