Service manual

SiENBE12-522A Troubleshooting
Service Diagnosis 219
5.11 OL Activation (Compressor Overload)
Remote
Controller
Display
E5
Outdoor Unit LED
Display
A 5 1 4 2 1 3 4 4 1
Method of
Malfunction
Detection
A compressor overload is detected through compressor OL.
Malfunction
Decision
Conditions
" If the compressor OL is activated twice, the system will be shut down.
" The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
The operating temperature condition is not specified.
Supposed
Causes
" Refrigerant shortage
" Four way valve malfunctioning
" Outdoor unit PCB defective
" Water mixed in the local piping
" Electronic expansion valve defective
" Stop valve defective
Troubleshooting
Check No.04
Refer to P.245
Check No.05
Refer to P.246
Check No.06
Refer to P.247
Check No.11
Refer to P.250
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the valve itself or
the coil.
Replace the four way valve
coil or the valve itself.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
(R4697)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Discharge pipe thermistor
disconnected?
YES
Malfunctioning
Discharge pipe thermistor
NO
Functioning
Functioning
Check No. 11
Check the refrigerant line.
Malfunctioning
Refrigerant shortage
Water mixed
Stop valve defective
Check No. 06
Check the thermistors
Malfunctioning
Functioning
Check No. 04
Check the electronic expantion
valve.
Malfunctioning
Functioning
Check No. 05
Check the four way valve.
Replace the outdoor unit
PCB.