Service manual

Table Of Contents
Troubleshooting Based on Equipment Condition Si42-107
74 Troubleshooting
 "&:55"
%":"+"
/,*
:"
! 600
! 0(
! 6
! (06(
! (
! 660
! :60(
! 8
4:";
Malfunction of fan
motor
Check the magnetic
switch and aux. switch
for fan motor
Replace fan motor.
Remove the disturbing
item
Cleaning of the heat
exchanger
After vacuum drying,
charge correct amount
of refrigerant
Check the pressure
switch
Possible causes as
follows:
* Refrigerant overcharge
* Mixing of air in
refrigerant system
* Faulty pressure switch
Does the
fan rotate?
Does the fan
overheated?
NO
Is there any
item disturbing
airflow?
NO
NO
Is the heat
exchanger soiled?
NO
YES
YES
YES
YES
Outdoor unit
[
[
(S1271)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.