Service manual

Table Of Contents
Troubleshooting by Remote Controller Display / LED Display Si42-107
254 Troubleshooting
Does
outdoor unit
microcomputer
normal H1P
blink?
Is
indoor-outdoor
transmission wire wired
correctly?
Is H1P blinking?
NO YES
NO
NO
NO
NO (ON or OFF)
NO (OFF)
YES
YES
YES
Is HAP blinking?
Is HBP blinking?
To outdoor unit
(next page)
Is H2P on?
Check of
indoor unit
microcom-
puter
normal
HAP
Check of
indoor unit
transmission
malfunction
HBP
YES
YES
Turn the power supply off
once and then back on.
Failure of indoor unit PC board or
malfunction of power supply
system
Resets normally.
Could be outside
cause (noise, etc.).
Failure of indoor unit PC board.
Wire correctly.
(P1386)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.