Troubleshooting Based on Equipment Condition Si42-107
216 Troubleshooting
4:";
Normal. Unit is in 3-min standby
mode
Contact power company
Check compressor
Replace power cable
Clogging of capillary tube
Four-way valve malfunction
Check compressor
Turn the operation switch
ON and OFF, then wait at
ON side.
Check on the cause why
overcurrent relay (for
compressor) or
compressor protection
thermostat acted.
After vacuum drying,
charge correct amount of
refrigerant. Then, start
operation again.
NO
YES
YES
YES
Malfunction of
compressor
YES
YES
Is the
discharge side of
compressor hot after
unit operation
stop?
Is
there any
temperature
difference between inlet
and outlet of
capillary
tube?
Is there
any temperature
difference between
suction side and delivery
side offour-way
valve?
Power
supply voltage is
within ±10 % of specified
voltage.
Is the size
of power cable
through total length
correct?
Does the unit
start operation after
3 minutes?
NO
NO
NO
NO
YES
[Electric system]
[Refrigerant circuit]
Not so hot
NO
(S1359)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.