Specifications
Installation of indoor unit EDUS281104
96 Installation of indoor / outdoor unit
3PN06240-3E
11
9-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A) MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW) FLA: Full Load Amps (A)
9-3 SPECIFICATIONS FOR FIELD SUPPLIED
FUSES AND WIRES
Allowable length of transmission wire and remote controller wire
are as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280 ft.
(2) Indoor unit – Remote controller:
Max. 1640 ft.
10. WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER
10-1 HOW TO CONNECT WIRES
〈
〈〈
〈Methods of wiring power supply, units and connecting
remote controller wires〉
〉〉
〉
• Power supply wire
Remove the control box lid (2) and connect wires to the
power supply terminal block (3P) inside. In doing this, pull the
wires inside through rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A
as before.
• Transmission wire and remote controller wire
Remove the control box lid (1) and pull the wires inside
through rubber bush B and connect to the transmission ter-
minal block (6P).
• After connection, attach sealing pad
(Be sure to attach it to prevent water from infiltrating the unit
from the outside.)
CAUTION
• Even if the control box lid (1)(2) is removed, pull the remote
controller wire, transmission wire and the power supply wire
inside the unit so that the wires do not come into contact with
the opening section of the metal casing.
• Pass conduits through the wall and secure along with the
refrigerant pipe in order to prevent external pressure being
applied to transmission wire and power supply wire.
• Arrange the wires and fix a lid firmly so that the lid does not
float during wiring work.
• Do not clamp remote controller wire and transmission wire
together with power supply wire. Doing so may cause mal-
function.
• Remote controller wire, transmission wire and power supply
wire should be located at least 5 in. from other electric wires.
Not following this guideline may result in malfunction due to
electrical noise.
Units
Power
supply
Fan motor
Model Hz Volts
Voltage
range
MCA MFA KW FLA
FCQ24MVJU
60
208-
230V
Max. 253
Min. 187
1.3 15 0.09 1.0
FCQ30MVJU
1.3 15 0.09 1.0
FCQ36MVJU
1.4 15 0.09 1.1
FCQ42MVJU
1.4 15 0.09 1.1
Model
Power supply wiring
Transmission
wiring
Field fuses
Size Wire Size
FCQ24MVJU
15A
Wire size
must
comply with
local codes.
Sheathed wire
(2 wires)
AWG
18-16
FCQ30MVJU
FCQ36MVJU
FCQ42MVJU
〈 〉