Specifications
EDUS281104 Installation of indoor unit
Installation of indoor / outdoor unit 89
3PN06240-3E
4
2-1 ACCESSORIES
Check the following accessories are included with your unit.
2-2 OPTIONAL ACCESSORIES
• The optional decoration panel and remote controller are
required for this indoor unit.
Table 1
Table 2
FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
b. Items to be checked at time of delivery
Also review the “SAFETY CONSIDERATIONS”
2-3 NOTE TO INSTALLER
• Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
3. SELECTING INSTALLATION SITE
Please attach additional thermal insulation material to the unit
body when it is believed that the relative humidity in the ceiling
exceeds 80%. Use glass wool, polyethylene foam, or similar
with a thickness of 3/8 in.. or more as thermal insulation mate-
rial.
(1) Select an installation site where the following conditions are
fulfilled and that meets with your customer’s approval.
• In the upper space (including the back of the ceiling) of the
indoor unit where there is no possible dripping of water
from the refrigerant pipe, drain pipe, water pipe, etc.
• Where optimum air distribution can be ensured.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service
can be ensured.
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual of the outdoor unit.)
Name
(1) Drain
hose
(2) Metal
clamp
(3) Washer for
hanger
bracket
(4) Clamp
Quantity 1 pc. 1 pc. 8 pcs. 4 pcs.
Shape
Name
(5) Paper
pattern for
installation
(6) Screws
(M5)
(7) Washer
fixing plate
Insulation for
fitting
Quantity 1 pc. 4 pcs. 4 pcs. 1 each
Shape
Also used as
packing
material
For paper
pattern for
installa-
tion
(8) for gas
pipe
(9) for liquid
pipe
Name Sealing pad
(Other)
• Installation manual
• Operation manual
Quantity 1 each 2 pcs.
Shape
(10) Large
(11) Medium
(12) Small
Model
Optional decoration panel
Color White
FCQ24 · 30 · 36 · 42MVJU BYC125K-W1
Remote controller
Wired type BRC1C71
Wireless type BRC7C812
Items to be checked
If not properly done, what is
likely to occur.
Check
Are the indoor and outdoor unit
fixed firmly?
The units may drop, vibrate or
make noise.
Is the gas leak test finished?
It may result in insufficient cool-
ing.
Is the unit fully insulated? Condensate water may drip.
Does drainage flow smoothly? Condensate water may drip.
Does the power supply voltage
correspond to that shown on
the name plate?
The unit may malfunction or
the components burn out.
Are wiring and piping correct?
The unit may malfunction or
the components burn out.
Is the unit safely grounded? It may result in electric shock.
Is wiring size according to
specifications?
The unit may malfunction or
the components burn out.
Is something blocking the air
outlet or inlet of either the
indoor or outdoor units?
It may result in insufficient cool-
ing.
Are refrigerant piping length
and additional refrigerant
charge noted down?
The refrigerant charge in the
system is not clear.
Items to be checked Check
Did you explain about operations while showing the operation
manual to your customer?
Did you hand the operation manual over to your customer?