Specifications
EDUS281104 Capacity tables
RZR-P, RZQ-P(9) 59
FHQ42MVJU + RZQ42PVJU9
Cooling Capacity
230V–60Hz
Indoor Air
Temp.
Outdoor Air Temp. ˚FDB
EDB(˚FDB) EWB(˚FWB)
68.0
72.0
77.0
80.0
86.0
90.0
57.0
61.0
64.0
67.0
72.0
75.0
26.3
32.0
36.2
40.5
46.8
47.6
1.66
2.02
2.31
2.67
3.26
3.28
26.3
32.0
36.2
40.5
45.1
45.9
1.81
2.29
2.70
3.15
3.62
3.64
26.3
32.0
36.2
40.5
43.5
44.3
2.09
2.67
3.15
3.68
3.98
4.01
26.3
32.0
36.2
40.5
42.7
43.5
2.22
2.85
3.37
3.95
4.14
4.17
26.3
32.0
36.2
40.5
41.8
42.6
2.40
3.09
3.67
4.30
4.35
4.38
26.3
32.0
36.2
38.9
40.2
41.0
2.76
3.58
4.26
4.66
4.72
4.75
68 77 86 90 95 104
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
Heating Capacity
230V–60Hz
Indoor Air
Temp.
Outdoor Air Temp. ˚FWB
EDB(˚FDB)
61
64
68
70
72
75
3.48
3.58
3.71
3.78
3.85
3.95
29.0
29.0
28.9
28.8
28.8
28.7
32.4
32.3
32.2
32.2
32.1
32.1
3.71
3.80
3.92
3.98
4.04
4.13
35.7
35.6
35.5
35.5
35.5
35.4
3.90
3.98
4.09
4.15
4.20
4.28
39.8
39.7
39.6
39.5
38.0
35.8
4.09
4.17
4.26
4.30
4.12
3.85
42.3
42.3
41.0
39.5
38.0
35.8
4.20
4.26
4.17
4.00
3.84
3.59
14 23 32 43 50
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
Cooling
Indoor : 80˚FDB, 67˚FWB
Outdoor : 95˚FDB
Heating
Indoor : 70˚FDB
Outdoor : 47˚FDB, 43˚FWB
Equivalent Piping Length
25ft (Level Difference : 0)
Hz, Volts
60Hz, 230V
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3. shows nominal MAX capacities