Specifications
Capacity tables EDUS281104
50 RZR-P, RZQ-P(9)
FCQ30PVJU + RZR30PVJU
FCQ36MVJU + RZR36PVJU
FCQ42MVJU + RZR42PVJU
Cooling Capacity
230V–60Hz
Indoor Air
Temp.
Outdoor Air Temp. ˚FDB
EDB(˚FDB) EWB(˚FWB)
68 77 86 90 95 104
TC
kBTUH
SHC
MBh
PI
kW
TC
kBTUH
SHC
MBh
PI
kW
TC
kBTUH
SHC
MBh
PI
kW
TC
kBTUH
SHC
MBh
PI
kW
TC
kBTUH
SHC
MBh
PI
kW
TC
kBTUH
SHC
MBh
PI
kW
Cooling
Indoor : 80˚FDB, 67˚FWB
Outdoor : 95˚FDB
Equivalent Piping Length
25ft (Level Difference : 0)
Hz, Volts
60Hz, 230V
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. shows nominal MAX capacities
68.0
72.0
77.0
80.0
86.0
90.0
57.0
61.0
64.0
67.0
72.0
75.0
19.47
23.68
26.84
30.00
34.65
35.24
16.8
20.1
21.2
23.1
24.4
22.2
1.24
1.50
1.71
1.97
2.39
2.40
19.47
23.68
26.84
30.00
33.43
34.02
16.8
20.1
21.2
23.1
23.7
21.4
1.35
1.69
1.99
2.31
2.64
2.66
19.47
23.68
26.84
30.00
32.21
32.80
16.8
20.1
21.2
23.1
22.9
20.7
1.55
1.96
2.31
2.69
2.91
2.92
19.47
23.68
26.84
30.00
31.66
32.25
16.8
20.1
21.2
23.1
22.5
20.4
1.64
2.09
2.47
2.88
3.02
3.04
19.47
23.68
26.84
30.00
30.99
31.58
16.8
20.1
21.2
23.1
22.1
19.9
1.77
2.26
2.68
3.13
3.17
3.19
19.47
23.68
26.84
28.78
29.77
30.36
16.8
20.1
21.2
22.1
21.2
19.2
2.03
2.61
3.11
3.39
3.43
3.46
Cooling Capacity
230V–60Hz
Indoor Air
Temp.
Outdoor Air Temp. ˚FDB
EDB(˚FDB) EWB(˚FWB)
68.0
72.0
77.0
80.0
86.0
90.0
57.0
61.0
64.0
67.0
72.0
75.0
23.4
28.4
32.2
36.0
41.6
42.3
1.56
1.89
2.15
2.48
3.02
3.03
23.4
28.4
32.2
36.0
40.1
40.8
1.69
2.13
2.51
2.91
3.35
3.37
23.4
28.4
32.2
36.0
38.6
39.4
1.94
2.47
2.92
3.41
3.68
3.70
23.4
28.4
32.2
36.0
38.0
38.7
2.07
2.64
3.12
3.65
3.83
3.85
23.4
28.4
32.2
36.0
37.2
37.9
2.23
2.86
3.39
3.97
4.02
4.04
23.4
28.4
32.2
34.5
35.7
36.4
2.56
3.31
3.94
4.30
4.36
4.39
68 77 86 90 95 104
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
Cooling
Indoor : 80˚FDB, 67˚FWB
Outdoor : 95˚FDB
Equivalent Piping Length
25ft (Level Difference : 0)
Hz, Volts
60Hz, 230V
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. shows nominal MAX capacities
Cooling Capacity
230V–60Hz
Indoor Air
Temp.
Outdoor Air Temp. ˚FDB
EDB(˚FDB) EWB(˚FWB)
68.0
72.0
77.0
80.0
86.0
90.0
57.0
61.0
64.0
67.0
72.0
75.0
26.3
32.0
36.2
40.5
46.8
47.6
1.94
2.36
2.70
3.12
3.80
3.82
26.3
32.0
36.2
40.5
45.1
45.9
2.11
2.68
3.15
3.67
4.22
4.24
26.3
32.0
36.2
40.5
43.5
44.3
2.44
3.11
3.68
4.29
4.64
4.67
26.3
32.0
36.2
40.5
42.7
43.5
2.59
3.32
3.93
4.60
4.83
4.86
26.3
32.0
36.2
40.5
41.8
42.6
2.80
3.60
4.28
5.01
5.07
5.10
26.3
32.0
36.2
38.9
40.2
41.0
3.22
4.17
4.97
5.43
5.50
5.54
68 77 86 90 95 104
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
TC
MBh
PI
kW
Cooling
Indoor : 80˚FDB, 67˚FWB
Outdoor : 95˚FDB
Equivalent Piping Length
25ft (Level Difference : 0)
Hz, Volts
60Hz, 230V
1. The above data are based on the following conditions.
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. shows nominal MAX capacities