Specifications
EDUS281104 Electrical characteristics
RZR-P, RZQ-P(9) 45
RZR36PVJU / RZR42PVJU
RZQ36PVJU9 / RZQ42PVJU9
NOTES:
1. RLA is based on the following conditions:
Power supply: 60 Hz, 208V-230V
Cooling:
I n d o o r t e m p : 8 0
°
FDB / 67
°
F W B ,
Outdoor temp: 95
°
FDB
Heating:
Indoor temp: 70
°
FDB
O u t d o o r t e m p : 4 7
°
FDB / 43
°
F W B
2. Voltage range:
Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not below
or above listed range limits.
3. Maximum allowable voltage variation between phases is
4. MCA represents maximum input current.
5. MOP represents capacity which may accept MCA.
6. Select wire size bsed on the value of MCA.
7. MOP is used to select the fuse, circuit breaker, or the
ground fault circuit interrupter (ground leakage circuit breaker).
Model Units Power Supply Comp. OFM
Outdoor
H/P
C/O
Hz Volts Min. Max MCA MOP MSC RLA KW FLA
RZQ36PVJU9 H/P 60 208/ 230 187 253 27.0 30 − 18.6
0.070
+
0.070
0.3 +0.3
RZQ42PVJU9 H/P 60 208/ 230 187 253 27.0 30 − 19.6
0.070
+
0.070
0.3 +0.3
RZR36PVJU C/O 60 208/230 187 253 27.0 30 − 18.6
0.070
+
0.070
0.3 +0.3
RZR42PVJU C/O 60 208/230 187 253 27.0 30 − 19.6
0.070
+
0.070
0.3 +0.3
SYMBOLS:
MCA: Minimum Circuit Amps. (A)
MOP: Maximum Overcurrent Protective
Device (A) (See Note 6)
MSC: Maximum current when starting the
compressor. (A)
RLA: Rate Load Amps (A)
OFM: Outdoor Fan Motor (A)
FLA: Full Load Amps (A)
KW: Fan Motor Rated Output
2%.