Specifications
Electrical characteristics EDUS281104
44 RZR-P, RZQ-P(9)
7.2 Outdoor unit
RZR18PVJU / RZR24PVJU / RZR30PVJU
RZQ18PVJU9 / RZQ24PVJU9 / RZQ30PVJU
Model Units Power Supply Comp. OFM
Outdoor
H/P
C/O
Hz Volts Min. Max MCA MOP MSC RLA W FLA
RZQ18PVJU9 H/P 60
208 187 229
16.5 20 _ 7.1 70 0.3
230 209 253
RZQ24PVJU9 H/P 60
208 187 229
16.5 20 _ 10.3 70 0.3
230 209 253
RZQ30PVJU H/P 60
208 187 229
16.5 20 _ 16.0 70 0.3
230 209 253
RZR18PVJU C/O 60
208 187 229
16.5 20 _ 7.1 70 0.3
230 209 253
RZR24PVJU C/O 60
208 187 229
16.5 20 _ 10.3 70 0.3
230 209 253
RZR30PVJU C/O 60
208 187 229
16.5 20 _ 16.0 70 0.3
230 209 253
NOTES:
1. RLA is based on the following conditions:
Power supply: 60 Hz, 208V-230V
Cooling:
Indoor temp: 80
°
FDB / 67
°
FWB,
Outdoor temp: 95
°
FDB
Heating:
Indoor temp: 70
°
FDB
Outdoor temp: 47
°
FDB / 43
°
FWB
2. Voltage range:
Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not below
or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
5. MOP represents capacity which may accept MCA.
6. Select wire size bsed on the value of MCA.
7. MOP is used to select the fuse, circuit breaker, or the ground
fault circuit interrupter (ground leakage circuit breaker).
SYMBOLS:
MCA : Min. Circuit Amps. (A)
MOP: Max. Overcurrent Protective Device (Note 7)(A)
MSC: Max current during compressor startup. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor (A)
FLA: Full Load Amps (A)
kW: Fan Motor Rated Output (kW)