Specifications

EDUS281104 Installation of outdoor unit
Installation of indoor / outdoor unit 153
3P281953-2A
3 English
This air conditioner is an appliance that should not be
accessible to the general public.
The wall thickness of fi eld-installed pipes should be
selected in accordance with the relevant local, state,
and national regulations.
Safety Precaution
The PCI Data Station is a class A product. In a domestic
environment this product may cause radio interference in
which case the user may be required to take adequate mea-
sures.
INTRODUCTION2.
Standard operation limit2-1
The fi gures below assume following operating conditions for
indoor and outdoor units:
Equivalent pipe length ................25 ft.
Level difference ..........................0 ft.
Cooling Heating
<b>
B
<c>
A
C
D
<a>
0
5
59
115
41
5050
43
70
95
81
50
23
77
60
67 8257
A Outdoor temperature (°FDB)
B Indoor temperature (°FWB)
C Outdoor temperature (°FWB)
D Indoor temperature (°FDB)
Range for continuous operation
Range for pull down operation
Range for warming up operation
Range for operation
Technical specifi cations2-2
(<a> and <b> in the table indicate the operating condition
(shown in the left fi gure).)
Model
RZQ18PVJU
RZR18PVJU
RZQ24PVJU
RZR24PVJU
RZQ30PVJU
RZR30PVJU
Precaution
Refrigerant
R410A
Power
208/230V 60Hz
[FAQ] Wall mounted
Cooling (MBh)
18.0 24.0 <a>
Heating (MBh)
(RZQ only)
20.0 26.0 <b>
[FCQ] Ceiling mounted
Cooling (MBh)
18.0 24.0 30.0 <a>
Heating (MBh)
(RZQ only)
20.0 27.0 34.0 <b>
[FHQ] Ceiling Suspended
Cooling (MBh)
18.0 24.0 30.0 <a>
Heating (MBh)
(RZQ only)
20.0 27.0 34.0 <b>
(RZQ only)
[FTQ] Air Handling Unit
Cooling (MBh)
Heating (MBh)
18.0
20.0
24.0
26.0
<a>
<b>
Dimensions
(inch)
30-5/16 × 35 7/16 × 12 5/8
H × W × D
Weight
(lb.) 150
Connections
Gas
(inch)
5/8
Liquid
(inch)
3/8
Electrical specifi cations2-3
(<c> in the table indicate the operating condition (shown in
the left fi gure).)
Model
RZQ18PVJU
RZR18PVJU
RZQ24PVJU
RZR24PVJU
RZQ30PVJU
RZR30PVJU
Precaution
Power
Phase
~
Frequency (Hz) 60
Voltage (V) 208/230
Voltage
tolerance
(%) ±10
Max.Overcurrent
Protective device
(A) 20
Min. Circuit Amps.
(A) 16.5 <c>
Compressor
Phase 3~
Frequency (Hz) 60
Voltage (V) 208/230
Accessories2-4
Confi rm that the following accessories are supplied.
Clamp Insulation tube
Cover
(Handle)
(Large-1) (Large-2) (Small-1) (Small-2)
(1 pc.) (2 pcs.) (1 pc.) (2 pcs.) (1 pc.)
Screw Conduit mounting plate Others
Installation manual
(1 pc.) (2 pcs.) (2 pcs.)