ESiEN05-04 Service Manual R-410A Sky-Air Indoor www.daikin.
ESiEN05-04 Service Manual R-410A Sky-Air Indoor www.daikin.
ESIEN05-04 Table of Contents 1 1 Introduction 1.1 1.2 About This Manual .................................................................................. Combination Overview ............................................................................ i–i i–ii Part 1 System Outline 1 2 3 General Outline 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 What Is in This Chapter? ........................................................................
ESIEN05-04 1 3 Functional Diagrams 3.1 3.2 3.3 3.4 4 4 5 5 What Is in This Chapter? ......................................................................... FCQ35, 50, 60B....................................................................................... FCQ71, 100, 125B................................................................................... FCQ71, 100, 125, 140D........................................................................... FFQ25, 35, 50, 60B ..............................
ESIEN05-04 6 PCB Layout 1 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 6.10 6.11 6.12 6.13 What Is in This Chapter? ........................................................................ FCQ35, 50, 60B ...................................................................................... FCQ71, 100, 125B .................................................................................. FCQ71, 100, 125, 140D .......................................................................... FFQ25, 35, 50, 60B ..........
ESIEN05-04 1 Part 2 Functional Description 1 Functional concept 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 3 4 What Is in This Chapter? ......................................................................... Functions of Thermistors ......................................................................... Forced Operating Mode (Emergency Operation)..................................... Outdoor Unit Identification Function ..........................................
ESIEN05-04 Part 3 Troubleshooting 1 Troubleshooting 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 2 What Is in This Chapter? ........................................................................ General Troubleshooting Flowchart ........................................................ Overview of General Problems ............................................................... Procedure of Self-Diagnosis by Remote Controller ................................ Fault-diagnosis by Wired Remote Controller ......
ESIEN05-04 1 4 Additional Checks for Troubleshooting 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 What Is in This Chapter? ......................................................................... Indoor Unit: Checking the Fan Motor Hall IC ........................................... Indoor Unit: Checking the Power Supply Wave Form.............................. Checking the Thermistors ........................................................................ Resistance Conversion Table (Ambient, Coil, Fin) ..........
ESIEN05-04 Part 4 Commissioning and Test Run 1 Pre-Test Run Checks 1.1 1.2 1.3 2 What Is in This Chapter? ........................................................................ Test Run Checks .................................................................................... Setting the Wireless Remote Controller .................................................. 4–3 4–4 4–5 3 Field Settings 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 3 1 What Is in This Chapter? .................................
ESIEN05-04 1 Part 5 Disassembly and Maintenance 1 Disassembly and Maintenance 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 3 4 What Is in This Chapter? ......................................................................... 5–3 FCQ35, 50, 60, 71B................................................................................. 5–4 FCQ100, 125B ......................................................................................... 5–6 FFQ25, 35, 50, 60B .....................
ESIEN05-04 Introduction Part 0 1 Introduction 1.1 About This Manual Target group This service manual is intended for and should only be used by qualified engineers. Purpose of this manual This service manual contains all the information you need to do the necessary repair and maintenance tasks for the R-410A Sky Air Indoor Units.
Introduction Combination Overview Q “2” stands for symmetrical twin combination. Q “3” stands for symmetrical triple combination. Q “4“ stands for symmetrical double twin combination. Q “P” stands for pair combination Q ‘’M’’ stands for multi combination Q ‘’T’’ stands for assymmetrical twin or triple combination The table below contains the possible combinations between indoor units and pair split outdoor units.
ESIEN05-04 The table below contains the possible combinations between indoor units and multi split outdoor units.
Introduction The table below contains the possible combinations between indoor units and Sky Air outdoor units.
ceiling suspended cassette FUQ71BV3B Wall mounted ceiling suspended Indoor unit FHQ35BUV1B FHQ71BUV3B FAQ71BV3B FAQ100BV3B T FHQ50BUV1B T T T T FHQ60BUV1B T T T T T T T T P FHQ100BUV3B P FUQ100BV3B P FHQ125BUV3B T FUQ125BV3B T P T T T T P P P P P P P P T P T P T T T P 2 P P 3 4 4 2 3 3 P P P P P RZQ250B7W1B RZQ200B7W1B Heat Pump RZQ140B7W1B Non Inverter RZQ125B7(8)V3B RZQ125B7W1B RZQ100B7(8)V3B RZQ100B7W1B RZQ71B7(8)V3B REQ125B7W1B REQ100B7V3B REQ100B7W1B
Introduction 1 ESIEN05-04 Combination matrix Possible indoor combination (Standard capacity for twin, triple and double twin operation) Twin Triple Double Twin Outdoor models 3 RZQ71B8V3B 35-35 (KHRQ22M20TA7) RZQ100B8V3B RZQ100B7W1B 50-50 (KHRQ22M20TA7) 35-35-35 (KHRQ127H7) RZQ125B8V3B RZQ125B7W1B 60-60 (KHRQ22M20TA7) 50-50-50 (KHRQ127H7) 35-35-35-35 (3x KHRQ22M20TA7) RZQ140B7W1B 71-71 (KHRQ22M20TA7) 50-50-50 (KHRQ127H7) 35-35-35-35 (3x KHRQ22M20TA7) 4 Notes: 1 5 vi Possible indoor
ESIEN05-04 Introduction Combination matrix Possible indoor combination (Standard capacity for twin, triple and double twin operation) Twin Triple Double Twin RZQ200B7W1B 100-100 (KHRQ22M20TA7) 60-60-60 71-71-71 (KHRQ250H7) 50-50-50-50 (3x KHQ22M20TA7) RZQ250B7W1B 125-125 (KHRQ22M20TA7) _ 60-60-60-60 (3x KHRQ22M20TA7) Outdoor models Notes: 1 3 Possible indoor types: Q FCQ50~125 Q FFQ50, 60 Q FHQ50~125 Q FBQ50~125 Q FUQ71~125 Q FAQ71, 100 Q FDQ125 4 5 2 Individual indoor capac
Introduction 1 ESIEN05-04 Combination matrix Possible indoor combination (Standard capacity for twin and triple operation) Twin Triple Outdoor models 3 RQ71B7V3/W1 RR71B7V3/W1 35-35 (KHRQ22M20TA7) _ _ RQ100B7V3/W1 RR100B7V3/W1 50-50 (KHRQ22M20TA7) 50-60 (KHRQ22M20TA7) RQ125B7W1 RR125B7W1 60-60 (KHRQ22M20TA7) 50-71 (KHRQ22M20TA7) Notes: 1 4 5 viii _ _ _ _ 35-71 (KHRQ22M20TA7) 35-35-35 (KHRQ127H7) _ _ _ _ 50-50-50 (KHRQ127H7) _ _ _ Possible indoor types: Q FCQ35~71 Q FFQ3
ESIEN05-04 1 4 Part 1 System Outline What is in this part? 3 This part contains the following chapters: Chapter See page 1–General Outline 1–3 2–Specifications 1–45 3–Functional Diagrams 1–55 4–Wiring Diagrams 1–61 5–Switch Box Layout 1–95 6–PCB Layout 1–107 4 5 Part 1 – System Outline 1–1
ESIEN05-04 11 3 5 1–2 Part 1 – System Outline
ESIEN05-04 General Outline Part 1 1 1 General Outline 1.1 What Is in This Chapter? Introduction General outline Part 1 – System Outline This chapter contains the following information on the indoor units: Q Outlook and dimensions Q Components 3 This chapter contains the following general outlines: General outline See page 1.2–FCQ35, 50, 60, 71B 1–4 1.3–FCQ100, 125B 1–6 1.4–FCQ71D 1–8 1.5–FCQ100, 125, 140D 1–10 1.6–FFQ25, 35, 50, 60B 1–12 1.7–FBQ35, 50B 1–14 1.
see note 3 1–4 2. When installing an optional accessory, refer to the installation drawings. - For the fresh air intake kit ..... an inspection port is necessary - For the high efficiency filter ..... an inspection port is necessary - For the branch duct chamber ....
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
see note 3 1–6 2. When installing an optional accessory, refer to the installation drawings. - For the fresh air intake kit ..... an inspection port is necessary - For the high efficiency filter ..... an inspection port is necessary - For the branch duct chamber .... an inspection port is necessary NOTES: 1. Location of the nameplates: - Unit body: on the bell mouth at the inside of the suction grill. - Decoration panel: on the panel frame at the inside of the suction grill.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–8 Adjustable (0~550) 35 or less 4. Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured. 3.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–10 Adjustable (0~055) Branch duct connection 35 or less 4. Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured. 3.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–12 Adjustable 4. Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the main unit and the ceiling opening so that the panel overlap allowance can be ensured. 3. When the temperature and humidity in the ceiling exceed 30°C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required. 2.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–14 3. For maintenance of the air filter, it is necessary to provide a service access panel according to the installation method. (Refer to the ‘Filter installation method’ drawing) 2. The required ceiling depth varies according to the configuration of the specific system. (On circumference) (Knock out hole) VIEW C P.C.D. Fresh air intake position 5 NOTES: 1. Refer to ‘Outlook drawing for installing optional accessories’ when installing optional accessories.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–16 3. For maintenance of the air filter, it is necessary to provide a service access panel according to the installation method. (Refer to the ‘Filter installation method’ drawing) (On circumference) (Knock out hole) VIEW C Fresh air intake position 5 2. The required ceiling depth varies according to the configuration of the specific system. P.C.D. 4 NOTES: 1. Refer to ‘Outlook drawing for installing optional accessories’ when installing optional accessories.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–18 3. For maintenance of the air filter, it is necessary to provide a service access panel according to the installation method. (Refer to the ‘Filter installation method’ drawing) 2. The required ceiling depth varies according to the configuration of the specific system. (On circumference) (Knock out hole) P.C.D. 5 VIEW C Fresh air intake position (Service Space) or more Suspension bolt 4 VIEW B Outlook and dimensions VIEW A 1.9 NOTES: 1.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
General Outline 11 1.10 ESIEN05-04 FDQ125B The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
General Outline 11 1.11 ESIEN05-04 FDQ200, 250B The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–24 (Required space) Drain pipe connection (For left piping) (Required space) For height installation 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail. The front (Hanging position) or more Brand name plate (Note 2) (Service Space) 5 NOTES: 1. Location of unit’s Name plate: Bottom of fan housing inside the suction grill.
ESIEN05-04 Components Part 1 – System Outline General Outline 1 The table below contains the different components of the unit. No.
1–26 Drain pipe connection (For left piping) (Required space) or more From the floor side 2500 or more (Required space) For height installation 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail. Brand name plate (Note 2) 4 Floor side The front or more (Service Space) 3 NOTES: 1. Location of unit’s Name plate: Bottom of fan housing inside the suction grill.
ESIEN05-04 Components Part 1 – System Outline General Outline 1 The table below contains the different components of the unit. No.
1–28 (Required space) or more Floor side Drain pipe connection (For left piping) For height installation From the floor side 2500 or more (Required space) 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail. The front 4 Brand name plate (Note 2) or more (Service Space) 3 NOTES: 1. Location of unit’s Name plate: Bottom of fan housing inside the suction grill.
ESIEN05-04 Components Part 1 – System Outline General Outline 1 The table below contains the different components of the unit. No.
1–30 (Required space) or more Floor side Drain pipe connection (For left piping) (Hanging position) or more (Required space) For height installation 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail. The front Brand name plate (Note 2) or more (Service Space) 4 NOTES: 1. Location of unit’s Name plate: Bottom of fan housing inside the suction grill.
ESIEN05-04 Components Part 1 – System Outline General Outline 1 The table below contains the different components of the unit. No.
1–32 * 3. When closing the discharge grill (2 or 3 way discharge), direction of pipe connecion will be limited, please refer to Installation manual.) * or more or more *When closing the discharge grill, the required space is 30mm or more. (Note 3) Height of suspension bracket * or more Suspension bolt * or more or more (Required space) 4 2.In case of using infrared remote control, this is the position for the signal receiver. Refer to the drawing of infrared remote control for detail.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–34 3. When closing the discharge grill (2 or 3 way discharge), direction of pipe connecion will be limited, please refer to Installation manual.) * or more or more *When closing the discharge grill, the required space is 30mm or more. (Note 3) Height of suspension bracket * or more Suspension bolt * or more or more (Required space) 4 2.In case of using infrared remote control, this is the position for the signal receiver. Refer to the drawing of infrared remote control for detail. NOTES: 1.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–36 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail. hole Mounting Location 5 Approx. Approx. Approx. Name plate (Note 2) 50 OR MORE (Required space) 2500 OR MORE For installation in 50 or more (Required space) high spaces hole (Piping and Wiring intake) Piping direction 4 Outside line Piping direction 3 50 or more (Required space) Dimensions for full open front panel.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
or more 1–38 Detail A (Mounting hole for installation plate) Hole (For wood bolt) Mounting Location Approx. Approx. Approx. 5 Hole (For wood screw) Ceiling surface Oval hole (For wood screw) Oval hole (For wood screw) 4 Brand name plate (Note 2) 50 or more (Required space) hole (Piping and Wiring intake) or more (Service space for air filter) 2. In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of infrared remote control for detail.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
1–40 668 (Suspension position) 2. For maintenance of the air filter, it is necessary to provide a service access panel according to the installation method. (Refer to the ‘Filter installation method’ drawing). 1. Refer to ‘Outlook drawing for installing optional accessories’ when installing optional accessories. NOTES: 300 or more (Service space) B Suspension Bolt Outlook and dimensions VIEW A VIEW B 1.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
4 1–42 2. For maintenance of the air filter, it is necessary to provide a service access panel according to the installation method. (Refer to the ‘Filter installation method’ drawing). 1. Refer to ‘Outlook drawing for installing optional accessories’ when installing optional accessories. NOTES: 3 VIEW B (Service space) 5 B Suspension Bolt Outlook and dimensions VIEW A 1.
ESIEN05-04 Components General Outline 1 The table below contains the different components of the unit. No.
General Outline ESIEN05-04 11 3 4 5 1–44 Part 1 – System Outline
ESIEN05-04 Specifications Part 1 1 2 Specifications 2.1 What Is in This Chapter? Introduction Indoor units Part 1 – System Outline This chapter contains the following information: Q Technical specifications Q Electrical specifications 3 This chapter contains the following specifications: Specifications See page 2.2–FCQ – B 1–46 2.3–FCQ – D 1–47 2.4–FFQ – B 1–48 2.5–FBQ – B 1–49 2.6–FDQ – B 1–50 2.7–FHQ – B 1–51 2.8–FUQ – B 1–52 2.9–FAQ – B 1–53 2.
Specifications 11 2.2 ESIEN05-04 FCQ – B Technical specifications The table below contains the technical specifications. Specification Heat exchanger FCQ35B7V1 FCQ50B7V1 Rows x stages x fin pitch FCQ60B7V1 Face area 0.497 m² HIXA diam. 7 HiXSS diam.
ESIEN05-04 2.3 Specifications FCQ – D Technical specifications 1 The table below contains the technical specifications. Specification Heat exchanger FCQ71DV3B Rows x stages x fin pitch Face area FCQ100DV3B 2 x 10 x 1.2 mm FCQ140DV3B 2 x 12 x 1.2 mm 0.454 m² 0.
Specifications 11 2.4 ESIEN05-04 FFQ – B Technical specifications The table below contains the technical specifications. Specification Heat exchanger FFQ25B7V1B FFQ35B7V1B Rows x stages x fin pitch 3 0.269 m² Tube type HiXSS diam. 7 Multi louver fin Air flow rate cooling (high) 9.0 m³/min 10.0 m³/min 12.0 m³/min 15.0 m³/min Air flow rate cooling (low) 6.5 m³/min 6.5 m³/min 8.0 m³/min 10.0 m³/min Air flow rate heating (high) 9.0 m³/min 10.0 m³/min – 15.
ESIEN05-04 2.5 Specifications FBQ – B Technical specifications 1 The table below contains the technical specifications. Specification Heat exchanger FBQ35B7V1 FBQ50B7V1 FBQ60B7V1 Rows x stages x fin pitch Face area 0.132 m² Tube type 0.338 m² Hi-XSS diam. 7 Rhombus 11.5 m³/min 14.0 m³/min 19.0 m³/min 19.0 m³/min 27.0 m³/min 35.0 m³/min Air flow rate cooling (low) 9.0 m³/min 10.0 m³/min 14.0 m³/min 14.0 m³/min 20.0 m³/min 24.0 m³/min Air flow rate heating (high) 11.5 m³/min 14.
Specifications 11 2.6 ESIEN05-04 FDQ – B Technical specifications The table below contains the technical specifications. Specification Heat exchanger FDQ125B7V3B Rows x stages x fin pitch 3 x 14 x 1.75 mm 0.634 m² Tube type Hi-XSS diam. 7 Hi-XSS (8) Rhombus 43.0 m³/min 69 m³/min 89 m³/min Air flow rate heating 43.
ESIEN05-04 2.7 Specifications FHQ – B Technical specifications 1 The table below contains the technical specifications. Specification Heat exchanger Rows x stages x fin pitch FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B 2 x 12 x 1.75 mm 3 x 12 x 1.75 mm 2 x 12 x 1.75 mm Face area 0.182 m² FHQ125BUV1B 0.293 m² 0.341 m² 30.0 m³/min N-Hix Fin type Multi louver Air flow rate cooling (high) 13.0 m³/min 17.0 m³/min 17.0 m³/min 24.0 m³/min Air flow rate cooling (low) 10.0 m³/min 13.0 m³/min 14.
Specifications 11 2.8 ESIEN05-04 FUQ – B Technical specifications The table below contains the technical specifications. Specification Heat exchanger FUQ71BUV1B Rows x stages x fin pitch Face area 3 x 6 x 1.5 mm 0.353 m² N-Hix Fin type 3 Multi louver Air flow rate cooling (high) 19.0 m³/min 29.0 m³/min 32.0 m³/min Air flow rate cooling (low) 14.0 m³/min 21.0 m³/min 23.0 m³/min Air flow rate heating (high) 19.0 m³/min 29.0 m³/min 32.0 m³/min Air flow rate heating (low) 14.
ESIEN05-04 2.9 Specifications FAQ – B Technical specifications 1 The table below contains the technical specifications. Specification Heat exchanger Rows x stages x fin pitch FAQ71BUV1B FAQ100BUV1B 2 x 16 x 1.4 mm 2 x 12 x 1.4 mm Face area 0.289 m² 0.332 m² Tube type Hi-XA Fin type Fan N-Hix Multi louver Air flow rate cooling (high) 19.0 m³/min 23.0 m³/min Air flow rate cooling (low) 15.0 m³/min 19.0 m³/min Air flow rate heating (high) 19.0 m³/min 23.
Specifications 11 2.10 ESIEN05-04 FDEQ – B Technical specifications The table below contains the technical specifications. Specification Heat exchanger FDEQ71B7V3B Rows x stages x fin pitch FDEQ100B7V3B 3 x 14 x 1.75 mm Face area 0.226 m² Tube type Rhombus Air flow rate cooling (high) 16.0 m³/min 24.0 m³/min 30.0 m³/min Air flow rate cooling (low) 12.0 m³/min 17.0 m³/min 20.0 m³/min Air flow rate heating (high) 19.0 m³/min 28.0 m³/min 35.0 m³/min Air flow rate heating (low) 14.
ESIEN05-04 Functional Diagrams Part 1 1 3 Functional Diagrams 3.1 What Is in This Chapter? Introduction Functional diagrams This chapter contains the following information: Q Functional diagrams Q Pipe connection diameters. 3 This chapter contains the following functional diagrams: Functional diagram See page 3.2–Indoor Piping 1–56 3.3–Pipe Connection Diameters 1–58 3.
Functional Diagrams 11 3.
ESIEN05-04 Piping components (*) Remark Functional Diagrams 1 The table below contains the different components of the functional diagrams. No. Component Function / remark 1a Flare connection See pipe connection diameter. 2 Heat exchanger The heat exchanger is of the multi louvre fin type. Hi-X -tubes and coated waffle louvre fins are used.
Functional Diagrams 11 3.3 ESIEN05-04 Pipe Connection Diameters Indoor units The table below contains the refrigerant pipe connection diameters. ∅ Gas pipe (flare) ∅ Liquid pipe (flare) FCQ35B 9.5 mm 6.4 mm FCQ50, 60B 12.7 mm 6.4 mm FCQ71, 100, 125B 15.9 mm 9.5 mm FCQ71, 100, 125D 15.9 mm 9.5 mm FFQ25, 35B 9.5 mm 6.4 mm FFQ50, 60B 12.7 mm 6.4 mm FBQ35B 9.5 mm 6.4 mm FBQ50, 60B 12.7 mm 6.4 mm FBQ71, 100, 125B 15.9 mm 9.5 mm FDQ125B 15.9 mm 9.5 mm FDQ200B 28.6 mm 12.
ESIEN05-04 Part 1 1 3.4 Piping Components Components The table below contains the different components of the functional diagrams. No. Component Function / remark 1a Flare connection See pipe connection diameter. 2 Heat exchanger The heat exchanger is of the multi louvre fin type. Hi-X -tubes and coated waffle louvre fins are used.
ESIEN05-04 11 3 4 5 1–60 Part 1 – System Outline
ESIEN05-04 Wiring Diagrams Part 1 1 4 Wiring Diagrams 4.1 What Is in This Chapter? Introduction This chapter contains the wiring diagrams of the indoor units. Indoor units: This chapter contains the following wiring diagrams: Part 1 – System Outline 3 Wiring diagram See page 4.2–FCQ35, 50, 60B 1–62 4.3–FCQ71, 100, 125B 1–64 4.4–FCQ71, 100, 125, 140D 1–66 4.5–FFQ25, 35, 50, 60B 1–68 4.6–FBQ35, 50, 60B 1–70 4.7–FBQ71B 1–72 4.8–FBQ100, 125B 1–74 4.9–FDQ125, 200, 250B 1–76 4.
Wiring Diagrams 11 4.2 ESIEN05-04 FCQ35, 50, 60B Wiring diagram The illustration below shows the wiring diagram of the unit. indoor Wired remote control outdoor Norm.emerg.
ESIEN05-04 Wiring Diagrams 33H Float switch Wired remote control A1P Printed circuit board SS1 C1R Capacitor (M2F) 1 Selector switch (Main/Sub) F1U Fuse (5A, 250V) Receiver/display unit (attached to infrared remote control) HAP Light emitting diode (Service monitor-green) A2P, A3P M1A Motor (Swing flap) BS ON/OFF button M2F Motor (Indoor fan) H1P Light emitting diode (on-red) M3P Motor (Drain pump) H2P Light emitting diode (timer-green) Q1F Thermo switch (M2F embedded) H3P L
Wiring Diagrams 11 4.3 ESIEN05-04 FCQ71, 100, 125B Wiring diagram The illustration below shows the wiring diagram of the unit. indoor Wired remote control outdoor Norm.emerg.
ESIEN05-04 Wiring Diagrams S1L Float switch Receiver/display unit (attached to infrared remote control) A1P Printed circuit board A2P, A3P C1R Capacitor (M2F) BS ON/OFF button HAP Light emitting diode (Service monitor-green) H1P Light emitting diode (on-red) M1A Motor (Swing flap) H2P Light emitting diode (timer-green) M2F Motor (Indoor fan) H3P Light emitting diode (filter sign-red) M3P Motor (Drain pump) H4P Light emitting diode (defrost-orange) Q1F Thermo switch (M2F embedded
Wiring Diagrams 11 4.4 ESIEN05-04 FCQ71, 100, 125, 140D Wiring diagram The illustration below shows the wiring diagram of the unit. Receiver / Display Unit to Outdoor Unit Norm.Emg. Note 5 Note 5 Note 2 Central remote control 3 Wired remote control to Outdoor Unit In case of simultaneous operation system Indoor unit Indoor unit (Slave) (Master) 4 remote control Switch box (Indoor Unit) Notes 1. 5 : Terminal : Connector : Field wiring 2.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board (Power supply) Receiver/display unit (attached to infrared remote control) A2P Printed circuit board (Control) A4P A3P Printed circuit board (Humidity sensor unit) A5P Printed circuit board HAP Light emitting diode (Service monitor-green) BS1 Push button (ON/OFF) KPR Magnetic relay (M1P) H1P Light emitting diode (on-red) 1 Printed circuit board M1F Motor (Indoor fan) H2P Light emitting diode (timer-green) M1P Motor (Drain pump)
Wiring Diagrams 11 4.5 ESIEN05-04 FFQ25, 35, 50, 60B Wiring diagram The illustration below shows the wiring diagram of the unit. to Outdoor Unit In case of simultaneous operation system Indoor unit Indoor unit (Master) (Slave) to Outdoor Unit : Connector discrimination colour for components. : Connector colour for components. : Connector colour for printed circuit board. remote control 3 Note 3 4 Note 5 Wired remote control Note 3 Receiver / Display unit Notes 5 1.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1 Capacitor (M1F) R1T Thermistor (Air) F1U Fuse (F5A, 250V) SS1 Selector switch (Main/Sub) HAP Light emitting diode (Service monitor-green) KPR Magnetic relay (M1P) infrared remote control (Receiver/display unit) M1F Motor (Indoor fan) A3P Printed circuit board M1P Motor (Drain pump) A4P Printed circuit board M1S Motor (Swing flap) BS1 Push button (ON/OFF) Q1M Thermo switch (M1F embedded) H1P Light em
Wiring Diagrams 11 4.6 ESIEN05-04 FBQ35, 50, 60B Wiring diagram The illustration below shows the wiring diagram of the unit. 35,50,60,CLASS outdoor indoor Wired remote control 3 Details of Wired remote control (Optional accessory) 5 Compressor Operation 4 Fan Operation Terminals for Operation Indicator adapter for wiring Switch box Notes: 1. When using the central remote control, see manual for connection to the unit. 2. The remote control model varies according to the combination system.
ESIEN05-04 Wiring Diagrams 33H Float switch Wired remote control A1P Printed circuit board BS1 C1R Capacitor (Fan) BS2 Timer mode start/stop button F1U Fuse (5A, 250V) BS3, BS8 Programming time button F1T Thermal fuse (152°C) (M1F embedded) BS4, BS9 Temperature setting button 1 ON/OFF button HAP Light emitting diode (Service monitor-green) BS6 Operation mode selector button M1F Motor (Fan) BS7 Timer ON/OFF button M1P Motor (Drain pump) BS11 Fan speed control button R1T The
Wiring Diagrams 11 4.7 ESIEN05-04 FBQ71B Wiring diagram The illustration below shows the wiring diagram of the unit. 71 CLASS outdoor indoor Wired remote control 3 4 Fan Operation Details of Wired remote control (Optional accessory) Remote ON/OFF Forced OFF 5 Compressor Operation Terminals for Operation Indicator adapter for wiring Switch box Notes: 1. When using the central remote control, see manual for connection to the unit. 2.
ESIEN05-04 Wiring Diagrams S1L Float switch Wired remote control A1P Printed circuit board BS1 C1R Capacitor (Fan) BS2 Timer mode start/stop button F1T Thermal fuse (152°C) (M1F embedded) BS3, BS8 Programming time button HAP Light emitting diode (Service monitor-green) BS4, BS9 Temperature setting button M1F Motor (Fan) BS6 Operation mode selector button M1P Motor (Drain pump) BS7 Timer ON/OFF button R1T Thermistor (Air) BS11 Fan speed control button R2T Thermistor (Coil) B
Wiring Diagrams 11 4.8 ESIEN05-04 FBQ100, 125B Wiring diagram The illustration below shows the wiring diagram of the unit. 100,125 CLASS outdoor indoor Wired remote control 3 Fan Operation 4 Details of Wired remote control (Optional accessory) Remote ON/OFF Forced OFF 5 Compressor Operation Terminals for Operation Indicator adapter for wiring Switch box Notes: 1. When using the central remote control, see manual for connection to the unit. 2.
ESIEN05-04 Wiring Diagrams S1L Float switch Wired remote control A1P Printed circuit board BS1 C1R Capacitor (Fan) BS2 Timer mode start/stop button F1T Thermal fuse (152°C) (M1F embedded) BS3, BS8 Programming time button HAP Light emitting diode (Service monitor-green) BS4, BS9 Temperature setting button M1F Motor (Fan) BS6 Operation mode selector button M1P Motor (Drain pump) BS7 Timer ON/OFF button R1T Thermistor (Air) BS11 Fan speed control button R2T Thermistor (Coil) B
Wiring Diagrams 11 4.9 ESIEN05-04 FDQ125, 200, 250B Wiring diagram The illustration below shows the wiring diagram of the unit. 125 CLASS outdoor Wired remote control indoor 3 4 Details of Wired remote control 5 Switch box Remote ON/OFF Forced OFF Compressor Operation Fan Operation Terminals for Operation Indicator adapter for wiring : Terminal : Field wiring 1–76 Notes: : Protective earth (screw) 1. When using the central remote control, see manual for connection to the unit. 2.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board BS4 Temperature setting button up A3P Printed circuit board BS9 Temperature setting button down C1R Capacitor (Fan) BS6 Operation mode selector button F1T Thermal fuse (M1F embedded) BS7 Timer ON/OFF button HAP Light emitting diode (Service monitor-green) BS12 Inspection/test operation button K1F Magnetic contactor (M1F) BS14 Filter sign reset button M1F Motor (Fan) H1P Light emitting diode (Service monitor-red) R1T Thermist
Wiring Diagrams 11 4.10 ESIEN05-04 FHQ35, 50, 60B Wiring diagram The illustration below shows the wiring diagram of the unit. to Outdoor Unit In case of simultaneous operation system Indoor unit Indoor unit (Master) (Slave) : Connector discrimination colour for components. : Connector colour for components. : Connector colour for printed circuit board. remote control 3 to Outdoor Unit Note 4 4 Wired remote control Note 6 Note 4 Receiver / Display unit Note 6 5 Control box Notes 1.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1 Capacitor (M1F) R1T Thermistor (Air) F1U Fuse (F5A, 250V) SS1 Selector switch (Main/Sub) HAP Light emitting diode (Service monitor-green) KAR Magnetic relay (M1S) infrared remote control (Receiver/display unit) KPR Magnetic relay (M1P) A3P Printed circuit board M1F Motor (Indoor fan) A4P Printed circuit board M1S Motor (Swing flap) BS1 Push button (ON/OFF) Q1M Thermo switch (M1F embedded) H1P Light
Wiring Diagrams 11 4.11 ESIEN05-04 FHQ71, 100, 125B Wiring diagram The illustration below shows the wiring diagram of the unit. to Outdoor Unit In case of simultaneous operation system Indoor unit Indoor unit (Master) (Slave) remote control 3 to Outdoor Unit Note 4 Wired remote control 4 Note 6 Note 4 Receiver / Display unit Note 6 5 Notes Control box 1. : Terminal : Connector 2. : Field wiring 3.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board infrared remote control (Receiver/display unit) C1 Capacitor (M1F) A2P 1 Printed circuit board HAP Light emitting diode (Service monitor-green) A3P Printed circuit board KAR Magnetic relay (M1S) BS1 Push button (ON/OFF) KPR Magnetic relay (M1P) H1P Light emitting diode (on-red) M1F Motor (Indoor fan) H2P Light emitting diode (timer-green) M1S Motor (Swing flap) H3P Light emitting diode (filter sign-red) Q1M Thermo switch (M1
Wiring Diagrams 11 4.12 ESIEN05-04 FUQ71, 100, 125B Wiring diagram The illustration below shows the wiring diagram of the unit. In case of simultaneous operation system Indoor unit (Master) to Outdoor Unit Indoor unit (Slave) remote control 3 to Outdoor Unit Wired remote control Note 4 Norm.Emg. 4 Note 4 Receiver / Display unit 5 Notes 1. 2. : Terminal : Connector : Field wiring 3.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1 Capacitor (M1F) R1T Thermistor (Air) HAP Light emitting diode (Service monitor-green) SS1 Selector switch (Main/Sub) KAR Magnetic relay (M1S) KPR Magnetic relay (M1P) infrared remote control (Receiver/display unit) M1F Motor (Indoor fan) A2P Printed circuit board M1P Motor (Drain pump) A3P Printed circuit board M1S Motor (Swing flap) BS1 Push button (ON/OFF) Q1M Thermo switch (M1F embedded) H1P Ligh
Wiring Diagrams 11 4.13 ESIEN05-04 FAQ71B Wiring diagram The illustration below shows the wiring diagram of the unit. Receiver / Display unit Attached to infrared remote control) to Outdoor Unit Note 4 Note 4 In case of simultaneous operation system Indoor unit Indoor unit (Master) (Slave) Input from outside Note 2 Transmission wiring Central remote control to Outdoor Unit 3 Norm.Emg. Wired remote control 4 remote control Notes 1.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board infrared remote control (Receiver/display unit) HAP Light emitting diode (Service monitor-green) A2P Printed circuit board M1F Motor (Indoor fan) A3P Printed circuit board M1S Motor (Swing flap) BS1 Push button (ON/OFF) R1T Thermistor (Air) H1P Light emitting diode (on-red) R2T Thermistor (Coil) H2P Light emitting diode (timer-green) SS1 Selector switch (Emergency) H3P Light emitting diode (filter sign-red) X1M Terminal block
Wiring Diagrams 11 4.14 ESIEN05-04 FAQ100B Wiring diagram The illustration below shows the wiring diagram of the unit. In case of simultaneous operation system Indoor unit (Slave) to Outdoor Unit Indoor unit (Master) 3 remote control Wired remote control to Outdoor Unit Note 4 Norm. Emg. 4 5 Control box Notes 1. : Terminal : Connector 2. : Field wiring 3. In case using central remote control, connect it to the unit in accordance with the attached installation manual.
ESIEN05-04 Wiring Diagrams 1 A1P Printed circuit board infrared remote control (Receiver/display unit) A2P Printed circuit board (Transformer 230V/16V) A3P C1 Capacitor (M1F) A4P Printed circuit board HAP Light emitting diode (Service monitor-green) BS1 Push button (ON/OFF) KAR Magnetic relay (M1S) H1P Light emitting diode (on-red) KPR Magnetic relay (M1P) H2P Light emitting diode (timer-green) M1F Motor (Indoor fan) H3P Light emitting diode (filter sign-red) M1S Motor (Swing f
Wiring Diagrams 11 4.15 ESIEN05-04 FDEQ71B Wiring diagram The illustration below shows the wiring diagram of the unit.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1R Capacitor (Fan) BS1 F1T Thermal fuse (136°C) (T1R embedded) BS2 Timer mode start/stop button HAP Light emitting diode (Service monitor-green) BS3, BS8 Programming time button M1F Motor (Fan) BS4, BS9 Temperature setting button R1T Thermistor (Air) BS6 Operation mode selector button R2T Thermistor (Coil) BS7 Timer ON/OFF button RyF1-4 Magnetic relay (Fan) BS11 Fan speed control button RyP Magnetic r
Wiring Diagrams 11 4.16 ESIEN05-04 FDEQ100B Wiring diagram The illustration below shows the wiring diagram of the unit.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1R Capacitor (Fan) BS1 F1T Thermal fuse (136°C) (T1R embedded) BS2 Timer mode start/stop button HAP Light emitting diode (Service monitor-green) BS3, BS8 Programming time button M1F Motor (Fan) BS4, BS9 Temperature setting button R1T Thermistor (Air) BS6 Operation mode selector button R2T Thermistor (Coil) BS7 Timer ON/OFF button RyF1-4 Magnetic relay (Fan) BS11 Fan speed control button RyP Magnetic r
Wiring Diagrams 11 4.17 ESIEN05-04 FDEQ125B Wiring diagram The illustration below shows the wiring diagram of the unit.
ESIEN05-04 Wiring Diagrams A1P Printed circuit board Wired remote control C1R Capacitor (Fan) BS1 F1T Thermal fuse (136°C) (T1R embedded) BS2 Timer mode start/stop button HAP Light emitting diode (Service monitor-green) BS3, BS8 Programming time button M1F Motor (Fan) BS4, BS9 Temperature setting button R1T Thermistor (Air) BS6 Operation mode selector button R2T Thermistor (Coil) BS7 Timer ON/OFF button RyF1-4 Magnetic relay (Fan) BS11 Fan speed control button RyP Magnetic r
Wiring Diagrams ESIEN05-04 11 3 4 5 1–94 Part 1 – System Outline
ESIEN05-04 Switch Box Layout Part 1 1 5 Switch Box Layout 5.1 What Is in This Chapter? Introduction This chapter shows the switch box components. Indoor units This chapter contains the following switch box layouts: Part 1 – System Outline 3 PCB layout See page 5.2–FCQ35, 50, 60, 71B 1–96 5.3–FCQ100, 125B 1–97 5.4–FCQ71, 100, 125 140D 1–98 5.5–FFQ25, 35, 50, 60B 1–99 5.6–FBQ35, 50, 60, 71, 100, 125B 1–100 5.7–FDQ125, 200, 250B 1–101 5.8–FHQ35, 50, 60, 71, 100, 125B 1–102 5.
Switch Box Layout 11 5.
ESIEN05-04 5.
Switch Box Layout 11 5.
ESIEN05-04 5.
Switch Box Layout 11 5.
ESIEN05-04 5.
Switch Box Layout 11 5.
ESIEN05-04 5.
Switch Box Layout 11 5.
ESIEN05-04 5.
Switch Box Layout 11 5.
ESIEN05-04 PCB Layout Part 1 1 6 PCB Layout 6.1 What Is in This Chapter? Introduction Indoor units Part 1 – System Outline This chapter contains the following information: Q It describes which unit uses which PCB types Q It shows the PCB connectors 3 This chapter contains the following PCB layouts: PCB layout See page 6.2–FCQ35, 50, 60B 1–108 6.3–FCQ71, 100, 125B 1–109 6.4–FCQ71, 100, 125, 140D 1–110 6.5–FFQ25, 35, 50, 60B 1–112 6.6–FBQ35, 50, 60, 71B & FDEQ71B 1–113 6.
PCB Layout 11 6.2 ESIEN05-04 FCQ35, 50, 60B PCB The illustration below shows the PCB connectors. X20A X27A X11A X10A X33A X19A X60A X61A X5A X35A X24A 3 X15A X25A X18A X36A X40A X17A 4 Connectors 5 1–108 The table below describes the PCB connectors.
ESIEN05-04 6.3 PCB Layout FCQ71, 100, 125B PCB 1 The illustration below shows the PCB connectors. X27A X11A X33A X19A X10A X60A X61A X5A X35A X20A X24A X15A X18A X25A Connectors Part 1 – System Outline X36A 3 X40A 4 The table below describes the PCB connectors.
PCB Layout 11 6.4 ESIEN05-04 FCQ71, 100, 125, 140D PCB1 - Power PCB The illustration below shows the PCB1 connectors. X56A X54A X27A 3 X25A X55A X20A 4 Connectors 5 1–110 The table below describes the PCB connectors.
ESIEN05-04 PCB2 - Control PCB PCB Layout 1 The illustration below shows the PCB2 connectors. X36A X40A X57A X16A X30A X24A X18A X35A X15A 3 X58A Connectors Part 1 – System Outline X6A X33A 4 The table below describes the PCB connectors.
PCB Layout 11 6.5 ESIEN05-04 FFQ25, 35, 50, 60B PCB The illustration below shows the PCB connectors. X27A X11A X10A X33A X60A X61A X19A X20A X5A X35A X24A 3 X15A X25A X18A X36A X40A X17A 4 Connectors 5 1–112 The table below describes the PCB connectors. Connector Connected to Description X5A X1M Terminal strip for P1/P2 X10A T1R Transformer secondary side X11A T1R Transformer primary side X15A S1L Float switch X17A R3T Coil thermistor (gas). Not used on 71~125 class.
ESIEN05-04 6.6 PCB Layout FBQ35, 50, 60, 71B & FDEQ71B PCB 1 The illustration below shows the PCB connectors. X61A X60A X33A X11A X25A X27A X15A X18A X19A X21A 3 X17A 4 X10A X35A Connectors Part 1 – System Outline X5A X40A The table below describes the PCB connectors.
PCB Layout 11 6.7 ESIEN05-04 FBQ100, 125B & FDEQ100, 125B PCB The illustration below shows the PCB connectors. X61A X60A X33A X11A X25A X27A X15A 3 X18A X21A X19A 4 X10A X35A Connectors 5 1–114 X40A X5A The table below describes the PCB connectors.
ESIEN05-04 6.8 PCB Layout FDQ125, 200, 250B PCB 1 The illustration below shows the PCB connectors.ì X61A X33A X11A X27A X60A X31A X18A 3 X19A X21A X10A X35A Connectors Part 1 – System Outline X40A 4 X5A The table below describes the PCB connectors.
PCB Layout 11 6.9 ESIEN05-04 FHQ35, 50, 60B PCB The illustration below shows the PCB connectors. X61A X60A X33A X11A X27A X14A X15A X40A X20A X23A 3 X29A X18A X25A X19A X17A 4 X35A Connectors 5 1–116 X10A X5A X24A X26A The table below describes the PCB connectors. Connector Connected to Description X5A X1M Terminal strip for P1/P2 X10A T1R Transformer secondary side X11A T1R Transformer primary side X14A S1Q Limit switch (Swing flap) X15A – Connector for float switch.
ESIEN05-04 6.10 PCB Layout FHQ71, 100, 125B PCB 1 The illustration below shows the PCB connectors. X61A X60A X33A X11A X27A X14A X15A X40A X20A X29A X18A X35A Connectors Part 1 – System Outline 3 X25A X19A X10A X5A X24A 4 X26A The table below describes the PCB connectors.
PCB Layout 11 6.11 ESIEN05-04 FUQ71, 100, 125B PCB The illustration below shows the PCB connectors. X61A X60A X11A X27A X14A X15A X20A 3 X29A X18A X25A X19A 4 X35A Connectors 5 1–118 X10A X5A X24A The table below describes the PCB connectors.
ESIEN05-04 6.12 PCB Layout FAQ71B PCB 1 The illustration below shows the PCB connectors. X27A X20A 3 X30A 4 X36A 5 X18A X19A Connectors The table below describes the PCB connectors.
PCB Layout 11 6.13 ESIEN05-04 FAQ100B PCB The illustration below shows the PCB connectors. X61A X60A X27A 3 X11A X19A 4 X98A X20A X24A X35A X25A X29A X5A X10A Connectors 5 X18A The table below describes the PCB connectors.
ESIEN05-04 4 Part 2 Functional Description What is in this part? This part contains information on the functions used to control the system. Understanding these functions is vital when diagnosing a malfunction that is related to the functional control.
ESIEN05-04 1 2 3 5 2–2 Part 2 – Functional Description
ESIEN05-04 Functional concept Part 2 1 1 Functional concept 2 1.1 What Is in This Chapter? Introduction Overview This chapter will explain more details about the various functions that are programmed for the Sky - Air R410A indoor units. 3 This chapter contains the following topics: Topic See page 1.2–Functions of Thermistors 2–4 1.3–Forced Operating Mode (Emergency Operation) 2–5 1.4–Outdoor Unit Identification Function 2–7 1.5–Simulated Operation Function 2–8 1.
Functional concept 1 1.2 ESIEN05-04 Functions of Thermistors Locating the thermistors R3T 2 R1T 3 R2T 4 5 Remark Sensor R3T on indoor coil of FCQ35~60B7V1, FFQ35~60BV1, FBQ35~60B7V1 & FHQ35~60BUV1 is not used when the indoor units are connected to sky-air outdoor units (RR, RQ, RZQ).
ESIEN05-04 1.3 Functional concept Forced Operating Mode (Emergency Operation) Purpose The table below describes the purpose of the forced operating mode. If... Starting conditions 1 Then... Q R/C is defective Q Indoor PCB is defective Q Outdoor PCB is defective Forced operating mode can be used to go to cooling or heating. In forced operating mode, the compressor is forced to operate until the defective indoor or outdoor PCB is back online.
Functional concept ESIEN05-04 1 Step Action 3 Switch ON the emergency switch on the outdoor PCB. 4 Set the emergency switch on the outdoor PCB to the forced mode you prefer (Cooling or Heating). 5 Turn ON the power supply.
ESIEN05-04 1.4 Functional concept Outdoor Unit Identification Function 1 Purpose The purpose of the outdoor unit identification function is to enable the indoor unit to automatically determine which operating mode has to be set in function of the type of connected outdoor unit (c/o or h/p).
Functional concept 1 2 1.5 ESIEN05-04 Simulated Operation Function Outline When a malfunction on one of the below thermistors occurs, operation will continue while displaying the applicable alarm on the remote-controller. Fin thermistor malfunction is only displayed when pressing the "Inspection" button on the remote-controller.
ESIEN05-04 1.6 Outline Functional concept Restart Standby 1 To prevent the compressor from frequently turning ON and OFF and allow pressure equalization, forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard timer). 2 Graph Thermostat OFF Compressor Restart standby complete ON OFF Electronic expansion valve OFF Oudoor unit fan 3 Moves to “Stop” or “Starting control” after completion of “Restart standby”.
Functional concept 1 1.7 ESIEN05-04 Automatic Restart Purpose The purpose of the auto-restart function is to automatically resume the same operating mode as when the unit was operating when the power supply is restored after a power failure. Do not use the "Automatic Restart" function to daily start/stop the unit. 2 Precautions when turning OFF power 3 Q When you have to turn OFF the power supply in order to carry out maintenance, make sure to turn the remote control's ON/OFF switch OFF firstly.
ESIEN05-04 1.8 Functional concept Using Conditions for remote control Thermostat 1 Applicable The remote control thermostat is only available in wired remote controls. Method Unlike with VRV units, the remote control sensor is standard disabled for sky-air units. The use of the remote control sensor can be enabled by changing field setting 10(20)-2-02 to 10(20)-2-01.
Functional concept ESIEN05-04 And assuming suction temperature has changed from 30°C to 18°C (F --> A): Body thermostat sensor is used for temperatures from 30°C to 25°C (F --> D). remote control thermostat sensor is used for temperatures from 25°C to 21°C (D --> B). Body thermostat sensor is used for temperatures from 21°C to 18°C (B --> A).
ESIEN05-04 1.9 Functional concept Forced Thermostat OFF Outline The unit will perform the forced thermostat off function in following conditions: Condition 1 (cooling) Thermostat off due to freeze-up prevention. 1 Prevent the indoor unit heat exchanger from freezing in cooling operation when one of the below conditions is applicable: Condition 2 (heating) Q Indoor unit heat exchanger temperature < -5°C for 1 minute continuously.
Functional concept 1 2 1.10 ESIEN05-04 Freeze Prevention Function Purpose In order to avoid formation of ice on the indoor unit heat exchanger in cooling and dry mode, the system automatically starts up a freeze prevention cycle when a number of specific conditions are fulfilled.
ESIEN05-04 1.11 Functional concept PMV Control 1 Applicable units All inverter R410A sky-air Outline When the automatic mode is selected on the remote-controller, the unit will automatically activate the PMV control. The PMV index is a calculated average comfort level. 2 Refer to ISO 7730 for details.
Functional concept 1 2 1.12 ESIEN05-04 Thermostat Control Purpose Based on the information received from the air return sensor, the thermostat control will decide the required operation status of the system. Thermostat control Cooling mode: Set point Thermostat ON –0.5 K +1 K Thermostat OFF 3 Heating mode: Set point Thermostat ON 4 +0.
ESIEN05-04 1.13 Functional concept Drain Pump Control 1 Purpose Control the water draining from the drain pan. Starting conditions The drain pump control starts the drain pump motor when one of the following conditions is fulfilled: Normal control Q Cooling operation is activated Q Abnormal high water level is detected in the drain pan 2 In normal control, the drain pump is turned ON at compressor starting and turned OFF 5 minutes after the compressor has stopped (residual operation).
Functional concept 1 Float switch activation during thermostat ON ESIEN05-04 1 The thermostat is immediately turned OFF. 2 The drain pump continues to operate for minimum 10 minutes (even if abnormality is solved within the 10 minutes). 3 If the float switch closes again within 80 seconds, cooling operation can restart within the 10 minutes recovery period.
ESIEN05-04 1.14 Functional concept Condensation Avoidance Control 1 Purpose Avoid condensation on the swing flap when the most downward position of the swing flap (position 4) is selected on the remote control. Applicable units This function is applicable for the FHQ units only. Method The condensation avoidance control will function in the following operating modes: Method Q Cooling (automatic) Q Dry keep.
Functional concept 1 2 1.15 ESIEN05-04 Draft Avoidance Control 1 Purpose Avoid draft for the customer by delaying transfer of the flap to the Po0 (horizontal) position for a certain amount of time when defrosting and in heating thermostat OFF. Heating thermostat OFF The time chart below illustrates the draft avoidance control 1 in heating thermostat OFF. When the flap starts to move, there can be a draft. The fan speed decreases to LL speed but it takes some time because of its inertia.
ESIEN05-04 1.16 Functional concept Draft Avoidance Control 2 1 Purpose The purpose of the draft avoidance control 2 is to avoid draft when the flap is moving. Starting conditions The draft avoidance control 2 is activated when: Time chart Q Hot start is finished, or Q Cold air prevention control is finished. 2 If the fan speed is set to "H", the fan turns at low speed for a certain amount of time.
Functional concept 1 1.17 Fan and Flap Operations Cooling operation Function 2 3 4 ESIEN05-04 The table below contains the fan and flap operations.
ESIEN05-04 1.
Functional concept 1 At compressor startup ESIEN05-04 Q In cooling: The indoor fan is operated at low speed until the low-pressure value reaches 6 bar. Q In heating: Hot startup controlWhen performing a startup, or after the defrosting cycle has been completed, the indoor fan will be controlled as to prevent cold air draft and secure the starting performance (quick pressure build-up). Indoor unit fan: OFF 2 Heating operation is turend on with remote control.
ESIEN05-04 4 Part 3 Troubleshooting What is in this part? 33 This part contains the following chapters: Chapter See page 1–Troubleshooting 3–3 2–Error Codes 3–31 1–Error Codes: System Malfunctions 3–3 4–Additional Checks for Troubleshooting 3–53 4 5 Part 3 – Troubleshooting 3–1
ESIEN05-04 1 33 5 3–2 Part 3 – Troubleshooting
ESIEN05-04 Troubleshooting Part 3 1 1 Troubleshooting 1.1 What Is in This Chapter? Introduction When a problem occurs, you have to check all possible malfunctions. This chapter gives a general idea of where to look for malfunctions. Not all repair procedures are described. Some procedures are considered common practice. Overview Part 3 – Troubleshooting 33 This chapter contains the following topics: Topic See page 1.2–General Troubleshooting Flowchart 3–4 1.
Troubleshooting 1 1.2 ESIEN05-04 General Troubleshooting Flowchart Find out the situation according to the following procedure when there is a request for service from the customer. Troubleshooting by remote controller malfunction code. Turn the power supply switch ON or replace the fuse. Wait until power failure is over. Refer to "Remote controller display malfunction code and contents".
ESIEN05-04 1.3 Troubleshooting Overview of General Problems 1 Overview Equipment Condition Remedy See page 3-6 See page 3-8 See page 3-10 7 8 9 10 11 12 Equipment does not operate. Fan operates, but compressor does not. Cooling/heating operation starts but stops immediately. Equipment operates but does not provide heating. Equipment discharges white mist. Equipment produces loud noise or shakes. Equipment discharges dust. remote control LCD displays “88.” Indoor swing flap does not operate.
Troubleshooting 1 1.3.
ESIEN05-04 Troubleshooting 1 Troubleshooting Is power switch OFF or fuse for power switch blown? NO Is there power failure? YES YES Turn on power switch or replace fuse. If high-harmonics circuit breaker is not used on inverter compressor, have the circuit breaker replaced. Wait until power returns.
Troubleshooting 1 1.3.
ESIEN05-04 Troubleshooting 1 Troubleshooting · Indoor unit fan runs at set airflow rate. · (In cooling operation) When air thermistor ambient temperature is higher than set temperature · (In heating operation) When air thermistor ambient temperature is lower than set temperature Is the power switch OFF or the fuse for power switch blown? YES Turn on the power switch or replace fuse. NO Is the heating switch turned on at outdoor temperature >30˚C Normal.
Troubleshooting 1 1.3.3 ESIEN05-04 Cooling/heating operation starts but stops immediately Applicable Model All models of SkyAir series Error Detection Method Error Generating Condition 33 Possible Cause 4 5 3–10 Q Excess charge of refrigerant Q Air intrudes into refrigerant system Q Faulty pressure switch Q Faulty magnetic switch for outdoor unit fan motor Q Faulty aux.
ESIEN05-04 Troubleshooting 1 Troubleshooting Is wired the operation Is the type of lamp of remote controller remote controller wired or flashing? wireless? Wireless YES Diagnose based on the error code on remote controller Is the operation lamp YES of indoor unit photo-sensing section flashing? [ Heating: Indoor unit ] NO Cooling: Outdoor unit NO Does the fan rotate? YES Is the filter soiled? YES Malfunction of fan motor Check the magnetic switch and aux.
Troubleshooting 1 1.3.6 ESIEN05-04 Equipment operates but does not provide heating Applicable Model All models of SkyAir series Error Detection Method Error Generating Condition 33 Possible Cause 4 5 3–12 Q Excess charge of refrigerant Q Air intrudes into refrigerant system Q Faulty pressure switch Q Faulty magnetic switch for outdoor unit fan motor Q Faulty aux.
ESIEN05-04 Troubleshooting 1 Troubleshooting YES Is the unit in defrost mode? Wait for a while. No abnormality NO Measure the temperature of suction air and supply air. Temperature difference = Suction air temp. – Supply air temp. Temperature difference for heating should be between 14 and 30˚C.
Troubleshooting 1 1.3.7 ESIEN05-04 Equipment discharges white mist Applicable Model All models of SkyAir series Error Detection Method Error Generating Condition 33 4 Possible Cause Q Humid installation site Q Installation site is dirty and with dense oil mists. Q Soiled heat exchanger Q Clogged air filter Q Malfunction of fan motor Troubleshooting Is the room temperature higher than set value in cooling operation? 5 YES Continue unit operation.
ESIEN05-04 1.3.8 Troubleshooting Equipment produces loud noise or shakes Applicable Model 1 All models of SkyAir series Error Detection Method Error Generating Condition Possible Cause Q Excess charge of refrigerant Q Air intrudes into refrigerant system Q Flushing noise due to refrigerant shortage. (Sound of shoo...
Troubleshooting 1 1.3.9 ESIEN05-04 Equipment discharges dust Applicable Model All models of SkyAir series Error Detection Method Error Generating Condition 33 Possible Cause Q Carpet Q Animal's hair Q Application (cloth shop,...) Troubleshooting 4 Does the trouble generate at the time YES of operation start again after extended period of operation? Dust collected inside the indoor unit are blown out. Cleaning for inside of indoor unit is necessary.
ESIEN05-04 Troubleshooting 1.3.10 remote control LCD displays "88" Applicable Model 1 All models of SkyAir series Error Detection Method Error Generating Condition Possible Cause 33 Troubleshooting Trouble generates just after power supply ON YES NO Is the position of (SS 1) on indoor unit PCB at "Emergency"? The unit is checking to confirm that remote controller is normal. Indication appears for short time. 4 YES Turn the switch to "Normal", and reset power supply.
Troubleshooting 1 33 ESIEN05-04 1.3.11 Swing flap does not operate Applicable Models FUQ, FHQ, FAQ100 Method of Malfunction Detection Utilizes ON/OFF of the limit switch when the motor turns. Malfunction Decision Conditions When ON/OFF of the micro switch for positioning cannot be reversed even through the swing flap motor for a specified amount of time (about 30 seconds). Remark Some functions can force the swing flap into a fixed position, altough swing mode is selected on the remote control.
ESIEN05-04 Troubleshooting 1 Troubleshooting Are the connectors correctly connected to X29A and X14A on the PC board? NO YES Is the limit switch’s transfer connector correctly connected? NO Connect correctly. Connect correctly. YES Turn the power supply off once and back on, and check whether the swing flap motor swings when the power supply is turned back on.
Troubleshooting 1 1.4 ESIEN05-04 Procedure of Self-Diagnosis by remote control The inspection/test button The following modes can be selected by using the [Inspection/Test Operation] button on the remote control. Indoor unit settings can be made. Q Filter sign time Q Air flow direction Q Others 33 Depress Inspection/Test Operation button for more than 4 seconds. Local setting mode Service mode Service data can be obtained.
ESIEN05-04 1.5 Troubleshooting Fault-diagnosis by Wired remote control Explanation 1 If operation stops due to malfunction, the remote control’s operation LED blinks, and malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are displayed when inspection mode is entered.) The malfunction code enables you to tell what kind of malfunction caused operation to stop. See page 3-26 for malfunction code and malfunction contents.
Troubleshooting 1 1.6 ESIEN05-04 Fault-diagnosis by infrared remote control Introduction Contrary to the wired remote control, the infrared remote control does not display the error code. Instead, the operation LED on the light reception section flashes. Checking To find the error code, proceed as follows: Step Action 1 Press the INSPECTION/TEST button to select “inspection”. The equipment enters the inspection mode. “0” flashes in the UNIT No. display.
ESIEN05-04 Troubleshooting Step Action 2 Press the UP or DOWN button and change the UNIT No. until the receiver of the remote control starts to beep. 1 UP DOWN 33 4 If you hear... Then... 3 short beeps Follow all steps below. 1 short beep Follow steps 3 and 4. Continue the operation in step 4 until you hear a continuous beep. This continuous beep indicates that the error code is confirmed. 1 continuous beep 3 5 There is no abnormality. Press the MODE selector button.
Troubleshooting 1 ESIEN05-04 Step Action 4 Press the UP or DOWN button to change the error code upper digit until the receiver of the remote control starts to beep. DOWN UP DOWN 33 UP 4 5 5 If you hear... Then... 2 short beeps The upper digit matches. 1 short beep No digits match. 1 continuous beep Both upper and lower digits match. Press the MODE selector button.The right “0” (lower digit) indication of the error code flashes.
ESIEN05-04 Troubleshooting Step Action 6 Press the UP or DOWN button and change the error code lower digit until the receiver of the remote control generates a continuous beep. 1 DOWN UP DOWN 33 UP 7 4 Press the MODE button to return to normal status. If you do not press any button for at least 1 min, the remote control returns automatically to normal status.
Troubleshooting 1 1.7 ESIEN05-04 Overview of Error Codes Malfunction Code A1 A3 A6 AF AJ Contents/Processing Remarks Failure of PC board ass’y for indoor unit Malfunction of drain water level system Indoor unit fan motor overload / overcurrent / lock (Note 1) Abnormal drain water level Activation of float switch during compressor off.
ESIEN05-04 1.8 Troubleshooting Troubleshooting by LED Indications on the Indoor Unit Foreword 1 Troubleshooting can be carried out by service monitor LED (green).
Troubleshooting 1 1.9 ESIEN05-04 Troubleshooting by remote control Display / LED Display c : LED blinks Explanation for Symbols / w : LED on / x : LED off / — : No connection with troubleshooting : High probability of malfunction { : Possibility of malfunction : Low probability of malfunction — : No possibility of malfunction (do not replace) 1.9.
ESIEN05-04 1.9.2 Troubleshooting System Malfunctions Outdoor Unit Malfunction remote control Display 1 Location of Malfunction Other than PC Board Contents of Malfunction Details of Malfunction (Reference Page) Transmission error (between indoor and outdoor unit) Transmission error (between indoor and remote control) Transmission error between “main” remote control and “sub” remote control Excessive indoor units connected to this system.
Troubleshooting 1 1.10 ESIEN05-04 Overview of the Indoor Safety Devices Thermal protector 33 4 Thermal fuse fan motor Abnormal Reset (automatic) FCQ35, 50, 60, 71B >130°C +/-5°C <83°C +/-20°C N.A. FCQ100, 125B >140°C +/-5°C <45°C +/-15°C N.A. FCQ71, 100, 125, 140D N.A. N.A. N.A. FFQ25, 35, 50, 60B >130°C +/-5°C <83°C +/-20°C N.A. FBQ35, 50, 60, 71,100, 125B N.A. N.A. >152 +/-2°C FDQ125, 200, 250B N.A. N.A.
ESIEN05-04 Error Codes Part 3 1 2 Error Codes 2.1 What Is in This Chapter? Introduction In the first stage of the troubleshooting sequence, it is important to correctly interpret the error code on the remote control display. The error code helps you to find the cause of the problem. Shutdown For some errors, the system only shuts down when the error occurs several times.
Error Codes 1 2.2 ESIEN05-04 Malfunctioning Indoor PCB (A1) Error code A1 LED indications The table below shows the LED indications. Operation HAP (green) HBP (green) c c c w c x w — x — Normal Malfunctioning 33 Error generation 4 5 The error is generated when the data from the EEPROM is not received correctly. EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds its content without power.
ESIEN05-04 2.3 Error Codes Malfunction of Drain Water Level System (A3) Error code A3 LED indications The table below shows the LED indications. Operation 1 HAP (green) HBP (green) Normal c c Malfunctioning c c Error generation The error is generated when the water level reaches its upper limit and when the float switch turns OFF.
Error Codes 1 ESIEN05-04 Troubleshooting Begin Is the unit a cassette or built-in type? Is the optional drain raising mechanism connected? No No Is the short-circuit connector connected to X15A on the indoor unit PCB? Yes Connect the Short-circuit connector. No Yes Yes Check the continuity of the short-circuit connector. 33 Yes Is a drain pump connected to the indoor unit PCB? No Is there continuity? Connect the drain pump.
ESIEN05-04 2.4 Error Codes Malfunctioning Drain System (AF) 1 Error code AF LED indications The table below shows the LED indications. Operation HAP (green) HBP (green) Normal c c Malfunctioning c c Error generation The error is generated when the float switch changes from ON to OFF while the compressor is OFF. Causes The possible causes are: Q Error in the drain pipe installation Q Malfunctioning float switch Q Malfunctioning indoor unit PCB.
Error Codes 1 2.5 ESIEN05-04 Indoor Unit Fan Motor Lock (A6) Error code A6 LED indications The table below shows the LED indications. Operation 33 HAP (green) HBP (green) Normal c c Malfunctioning c c Error generation The error is generated when the fan rotations are not detected while the output voltage to the fan is at its maximum.
ESIEN05-04 Error Codes 1 Troubleshooting Check the connections of X20A and X26A. Are X20A and X26A properly connected? No Connect X20A and X26A correctly. Yes 3 Unplug X26A and switch the power supply on. 4 Check the voltage between pins 1 and 3 of X26A. 5 Is there about 12 VDC? No Replace indoor unit PCB. Yes Check indoor unit fan motor and motor wiring.
Error Codes 1 2.6 ESIEN05-04 Malfunctioning Capacity Setting (AJ) Error code AJ LED indications The table below shows the LED indications. Operation 33 Error generation 4 5 HAP (green) HBP (green) Normal c c Malfunctioning c c The error is generated when the following conditions are fulfilled: Condition Description 1 Q The unit is in operation. Q The PCB’s memory IC does not contain the capacity code. Q The capacity setting adapter is not connected. Q The unit is in operation.
ESIEN05-04 Error Codes 1 Troubleshooting Check if the capacity setting adapter is plugged into X23A of the indoor PCB. Is the capacity setting adapter plugged into X23A of the indoor unit PCB? No Plug a capacitor setting adapter that matches the capacity of the unit into X23A. Yes 3 Switch the power supply off and back on again. Is "AJ" displayed on the remote controller? No 4 The malfunction was caused by a missing capacity resistor. Yes 5 Replace indoor unit PCB.
Error Codes 1 2.7 Thermistor Abnormality (C4, C5, C9) Error code 33 4 5 ESIEN05-04 LED indications The table below describes the two thermistor abnormalities. Error Description C4 Malfunctioning heat exchanger thermistor system. C5 Malfuncioning gaspipe thermistor system. C9 Malfunctioning suction air thermistor system. The table below shows the LED indications.
ESIEN05-04 Error Codes 1 Troubleshooting Check the connector connection. Is it connected properly? No Correct the connection. Yes 3 Check the thermistor resistance. Is it normal? No Replace the thermistor. 4 Yes Check the contact between thermistor and PCB. Is the contact OK? Yes Replace outdoor unit PCB. Caution Part 3 – Troubleshooting 5 No Correct contact C4: Indoor liquid pipe thermistor (R2T). C5: Gaspipe thermistor (R3T) C9: Air suction thermistor (R1T).
Error Codes 1 2.8 ESIEN05-04 Malfunctioning remote control Air Thermistor (CJ) Error code CJ LED indications The table below shows the LED indications. Operation 33 Error generation HAP (green) HBP (green) Normal c c Malfunctioning c c The error is generated when the remote control thermistor becomes disconnected or shorted while the unit is running. Even if the remote control thermistor is malfunctioning, the system can operate with the system thermistor.
ESIEN05-04 2.9 Error Codes Malfunctioning of Moisture Sensor System (CC) Remote controller display 1 CC Applicable models FCQ-D Method of malfunction detection Even if a malfunction occurs, operation still continues. Malfunction is detected according to the moisture (output voltage) detected by the moisture sensor.
Error Codes ESIEN05-04 1 33 4 5 3–44 Part 3 – Troubleshooting
ESIEN05-04 4 Part 4 Commissioning and Test Run 3 What is in this part? This part contains the following chapters: Chapter See page 2–Pre-Test Run Checks 4–11 3–Field Settings 4–17 4–Test Run and Operation Data 4–31 44 5 Part 4 – Commissioning and Test Run 4–1
ESIEN05-04 1 3 4 5 4–2 Part 4 – Commissioning and Test Run
ESIEN05-04 Error Codes: System Malfunctions Part 4 1 1 Error Codes: System Malfunctions 1.1 What Is in This Chapter? Introduction Overview Part 3 – Troubleshooting In the first stage of the troubleshooting sequence, it is important to correctly interpret the error code on the remote control display. The error code helps you to find the cause of the problem. 33 This chapter contains the following topics: Topic See page 1.
Error Codes: System Malfunctions 1 1.2 ESIEN05-04 Malfunction of Transmission between Indoor and Outdoor Unit (U4 or UF) Error code U4 or UF Error generation The error is generated when the microprocessor detects that the transmission between the indoor and the outdoor unit is not normal over a certain amount of time.
ESIEN05-04 Error Codes: System Malfunctions 1 Troubleshooting 2 Continued from previous page Is HAP flashing? Check of outdoor unit microcomputer normal HAP NO (ON or OFF) Turn the power supply off once and then back on. YES Is HAP flashing? YES Resets normally. Could be outside cause (noise...). 33 NO Is HAP on? YES Failure of outdoor unit PCB. 4 NO (OFF) Turn off the power supply, disconnect the NO.2 indoor-outdoor transmission wire, and turn power supply back on.
Error Codes: System Malfunctions 1 1.3 ESIEN05-04 Malfunction of Transmission between Indoor Unit and remote control (U5) Error code U5 Error generation The error is generated when the microprocessor detects that the transmission between the indoor unit and the remote control is not normal over a certain amount of time. Causes The possible causes are: 33 Q Malfunctioning remote control Q Malfunctioning indoor PCB Q Outside cause (noise...
ESIEN05-04 1.4 Error Codes: System Malfunctions Malfunction of Transmission between MAIN remote control and SUB remote control (U8) Error code 1 U8 Error generation The error is generated when, in case of controlling with two remote controls, the microprocessor detects that the transmission between the indoor unit and the remote controls (MAIN and SUB) is not normal over a certain amount of time.
Error Codes: System Malfunctions 1 1.5 ESIEN05-04 Malfunctioning Field Setting Switch (UA) Error code UA Error generation The error is generated when incorrect field settings have been set for pair/twin/triple/double twin. Causes The possible causes are: 33 Q Malfunctioning indoor or outdoor unit PCB Q Malfunctioning power supply PCB Q Indoor-outdoor, indoor-indoor unit transmission wiring Q Malfunctioning remote control wiring.
ESIEN05-04 Error Codes: System Malfunctions 1 Troubleshooting Is the remote control connected to more than one indoor unit? YES Connect the remote controller correctly. NO Is the outdoor unit used for Twin system? NO Check setting "No. of Connected Twin System Indoor Units" of indoor unit. YES Is the setting of Pair/Twin/Triple set correctly? NO 33 Set correctly.
Error Codes: System Malfunctions 1 1.6 Centralized Address Setting Error (UC) remote control Display 33 ESIEN05-04 UC Applicable Models All indoor unit models Method of Malfunction Detection Indoor unit microcomputer detects and judges the centralized address signal according to the transmission between indoor units.
ESIEN05-04 Pre-Test Run Checks Part 4 1 2 Pre-Test Run Checks 2.1 What Is in This Chapter? Introduction Overview This chapter contains the following information: Q Checks before test run Q Test run checks Q Setting the address for the receiver of the infrared remote control Q Setting the address for the infrared remote control 3 4 This chapter contains the following topics: Topic See page 2.2–Test Run Checks 4–12 2.
Pre-Test Run Checks 1 2.2 ESIEN05-04 Test Run Checks Checks before test run Before carrying out a test run, proceed as follows: Step Action 1 Make sure the voltage at the primary side of the safety breaker is: Q 2 Test run checks 3 4 5 4–12 230 V ± 10% Fully open the liquid and the gas stop valve. To carry out a test run, check the following: Q Check that the temperature setting of the remote control is at the lowest level in cooling mode or use test mode.
ESIEN05-04 2.3 Pre-Test Run Checks Setting the infrared remote control Introduction Setting the address for the receiver 1 To set the infrared remote control, you have to set the address for: Q The receiver of the infrared remote control Q The infrared remote control. The address for the receiver of the infrared remote control is factory set to 1. To change this setting, proceed as follows: Step Action 1 Turn OFF the power. 2 Remove the sealing pad on the top of the receiver.
Pre-Test Run Checks 1 Setting the address for the infrared remote control ESIEN05-04 The address for the infrared remote control is factory set to 1. To change this setting, proceed as follows: Step Action 1 Hold down the FILTER RESET button and the TEST button for at least 4 s, to go to field set mode. The display indicates the field set mode. 3 4 FILTER RESET TEST 5 2 Press the FAN button to select a multiple setting (A/b), see ‘Multiple settings A/b’ further in this section.
ESIEN05-04 Pre-Test Run Checks Step Action 3 Press the UP and DOWN buttons to set the address. Set the same address as the receiver (1, 2 or 3). The receiver does not work with addresses 4, 5 and 6. 1 UP DOWN 3 4 4 Press the RESERVE button to confirm the setting.
Pre-Test Run Checks 1 ESIEN05-04 Step Action 5 Press the TEST button to quit the field set mode and return to the normal display. ON / OFF TEMP TIME ˚C UP DOWN FAN RESERVE CANCEL TIMER 3 MODE SWING /TEST TEST 4 5 Multiple settings A/b When an outside control (central remote control...) controls an indoor unit, sometimes the indoor unit does not respond to ON/OFF and temperature settings commands from this controller.
ESIEN05-04 Field Settings Part 4 1 3 Field Settings 3.1 What Is in This Chapter? Introduction Overview This chapter contains the following information: Q How to change the field settings Q The field settings Q The factory settings. 3 This chapter contains the following topics: Topic See page 3.2–How to Change the Field Settings with the Wired remote control 4–18 3.3–How to Change the Field Settings with the infrared remote control 4–20 3.
Field Settings 1 3.2 ESIEN05-04 How to Change the Field Settings with the Wired remote control Installation conditions The field settings have to be changed with the remote control according to the installation conditions. Wired remote control The illustration below shows the wired remote control.
ESIEN05-04 Setting Field Settings 1 To set the field settings, you have to change: Q “Mode No.” Q “First code No.” Q “Second code No.”. To change the field settings, proceed as follows: Step Action 1 Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter the “Field setting mode”. 2 Press the TEMPERATURE CONTROL button until the desired “Mode No.” appears.
Field Settings 1 3.3 ESIEN05-04 How to Change the Field Settings with the infrared remote control Optional accessories If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed. Refer to OH98-2 or the installation manual (optional handbook) for each optional accessory. infrared remote control The illustration below shows the infrared remote control. UP button Mode No. Field setting mode 3 DOWN button RESERVE button First code No.
ESIEN05-04 3.4 Field Settings Overview of the Field Settings on the Indoor Units Field settings Mode No. 10 or 20 1 The table below contains the possible field settings of all indoor units. First code No. Second code No. Description of the setting 01 02 03 04 0 Filter counter Light contamination heavy contamination — — 1 Filter type Long Super long External Oil mist 2 Remote thermistor of the remote control TH1 = rem.
Field Settings 1 3.5 ESIEN05-04 Overview of the Factory Settings on the Indoor Units Factory settings Mode No. The table below contains the factory settings of all indoor units First code No. Second code No.
ESIEN05-04 3.6 Field Settings Setting the Ceiling Height Incorrectly setting 1 If you set the controller incorrectly, a connection mistake malfunction “UA” will appear on the remote control display. See ’Malfunctioning Field Setting Switch (UA)’ on page 3–8. Mode No. 13 or 23 First code No. 0 Set the second code No., according to the tables below. FHQ Second code No. Ceiling-suspended type 01 Height < 2.7 m 02 2.7 m < height < 3.5 m 03 Not used 3 FAQ Second code No.
Field Settings 1 3.7 ESIEN05-04 Setting the Filter Counter Mode No. 10 or 20 First code No. 0 When the filter counter indication time is set to ON, set the second code No., according to the table below Unit 3 Mode No. Fan speed setting at thermostat OFF 5 Second code No.
ESIEN05-04 Field Settings Note: Monitoring mode 1 ON THERMO OFF ON LL speed or set speed INDOOR FAN 3 OFF 6 min 6 min 1 min Air flow direction setting 1 min Set the air flow direction of the indoor units as given in the table below. This setting is needed when the optional air outlet blocking pad has been installed. The “Second code No” is factory set to “01”.
Field Settings 1 3.8 ESIEN05-04 MAIN/SUB Setting when Using Two remote controls Situation The MAIN/SUB setting is necessary when one indoor unit is controlled by two remote controls. When you use two remote controls (control panel and separate remote control), set one to MAIN and the other to SUB. You can do this by setting the switch on the remote control’s PCB. Setting The remote controls are factory set to MAIN, so you only have to change one remote control from MAIN to SUB.
ESIEN05-04 3.9 Field Settings Setting the Centralized Group No. 1 When? If you want to carry out centralized control with a central remote control and a unified ON/OFF controller, you have to set the group No. for each group with the remote control. Wired remote control The illustration below shows the wired remote control. Mode N° 3 UNIT No. Unit N° First Code N° Second Code N° GROUP Field set mode SETTING 4 4 3 1 7 5 6 Setting 5 2 To set the “Centralized group No.
Field Settings 1 3.10 ESIEN05-04 The Field Setting Levels Introduction The inspection level The three field setting levels are: Q Inspection level Q Monitoring level Q Maintenance mode settings. The inspection level is the highest level of the three field setting levels. You can change the views in the inspection level by pressing the INSPECTION/TEST button. The flow chart below explains the different windows of the inspection level.
ESIEN05-04 Possible system settings Field Settings The table below contains the possible system settings, which are displayed on the remote control if the TEST button is pushed twice shortly.
Field Settings Maintenance Mode Settings Mode No. The table below describes the maintenance mode settings. Function Content and operation method Example of the remote control display Display malfunction history 40 History error codes The history No. can be changed with the programming time button. Past error code Unit No. CODE SETTING 0: Newest Malfunction history - 1 ESIEN05-04 2: Oldest * “00” displayed for 3 and subsequent Select the display thermistor with the programming time button.
ESIEN05-04 Test Run and Operation Data Part 4 1 4 Test Run and Operation Data Introduction This chapter contains the following information: Q Overview General operation data 3 This chapter contains the following topics: Topic See page 4.
Test Run and Operation Data 1 4.1 ESIEN05-04 General Operation Data Guide Lines for Optimal Operation Condition The operation value guide lines when operating under standard conditions (at Rated frequency) by pushing the test run button on the remote control are as given in the table below.
ESIEN05-04 Test Run and Operation Data 1 Standard Conditions Indoor Unit Conditions 27°C DB/19°C WB 20°C DB Cooling Operation Heating Operation Outdoor Unit Conditions 35°C DB 7°C DB/6°C WB During or after maintenance, when the power supply is turned back on, operation restarts automatically by the “auto restart function.” Please exercise the proper caution.
Test Run and Operation Data 1 Correlation of Air-Conditioner’s Operation Status and Pressure / Running Current What happens in comparison to normal values is summarized in the table below. (Measured from 15 ~ 20 minutes or more after operation starts.
ESIEN05-04 4 Part 5 Disassembly and Maintenance 3 What is in this part? This part contains the following chapters: Chapter See page 1–Disassembly and Maintenance 5–3 4 55 Part 5 – Disassembly and Maintenance 5–1
ESIEN05-04 1 3 5 5–2 Part 5 – Disassembly and Maintenance
ESIEN05-04 Disassembly and Maintenance Part 5 1 1 Disassembly and Maintenance 1.1 What Is in This Chapter? Introduction Exploded views and components Dissassembly procedures This chapter contains the following information on the indoor units: Q Exploded views Q Components Q Disassembly procedures 3 This chapter contains the following topics: Topic See page 1.2–FCQ35, 50, 60, 71B 5–4 1.3–FCQ100, 125B 5–6 1.4–FFQ25, 35, 50, 60B 5–8 1.5–FBQ35, 50B 5–10 1.6–FBQ60, 71B 5–12 1.
Disassembly and Maintenance 1 1.2 ESIEN05-04 FCQ35, 50, 60, 71B Exploded view The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component B1 Heat exchanger assy E23 Drain pump B1.1 Branch pipe (FCQ35) E24 Float switch B1.1 Distributor with filter E25 Fan motor B1.2 Single union joint F1 Casing assy B1.3 Single union joint F6 Inspection cover assy B1.4 Flare nut F8 Drain pan assy B1.5 Flare nut F8.1 Drain plug B1.
Disassembly and Maintenance 1 1.3 ESIEN05-04 FCQ100, 125B Exploded view The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component B1 Heat exchanger assy E25 Fan motor B1.1 Distributor with filter F1 Casing assy B1.2 Single union joint F6 Inspection cover assy B1.3 Single union joint F8 Drain pan assy B1.4 Flare nut F8.1 Drain plug B1.
Disassembly and Maintenance 1 1.4 ESIEN05-04 FFQ25, 35, 50, 60B Exploded view The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No.
Disassembly and Maintenance FBQ35, 50B Fan assy 3 Accessories The illustration below shows the exploded view. Switch box Exploded view Drain pump assy 1 1.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 29 Plain washer 2 Right plate assy 30 Fitting bolt drain pump 3 Left plate assy 31 Fan assy 4 Interchangeable plate 31.1 Fan top plate 5 Small bottom plate 31.2 Fan housing bottom 6 Large bottom plate 31.3 Fan housing top 7 Air outlet flange 31.4 Rotor assy 8 Center stay assy 31.4.
Disassembly and Maintenance FBQ60, 71B The illustration below shows the exploded view. Fan assy 3 Accessories Switch box Exploded view Drain pump assy 1 1.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 29 Plain washer 2 Right plate assy 30 Fitting bolt drain pump 3 Left plate assy 31 Fan assy 4 Interchangeable plate 31.1 Fan top plate 5 Small bottom plate 31.2 Fan housing bottom 6 Large bottom plate 31.3 Fan housing top 7 Air outlet flange 31.4 Rotor assy 8 Center stay assy 31.4.
Disassembly and Maintenance FBQ100, 125B Fan assy 3 Accessories The illustration below shows the exploded view. Switch box Exploded view Drain pump assy 1 1.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 31 Fan assy 2 Right plate assy 31.1 Fan top plate 3 Left plate assy 31.2 Fan housing bottom 4 Interchangeable plate 31.3 Fan housing top 5 Small bottom plate 31.4 Rotor assy 6 Large bottom plate 31.5 Fan motor 7 Air outlet flange 31.6 Fan motor stand 8 Center stay assy 31.
Disassembly and Maintenance 1 1.8 ESIEN05-04 FDQ125, 200, 250B The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 6.22 Thermistor 2 Fan assy + fan mounting plate 6.23 Tie wrap with clip 3 Side plate right 6.24 PCB assy 4 Side plate left 6.25 Power supply transformer 5 Service cover assy 6.26 Earth wire 6 Switch box assy 6.27 Insulation switch box 6.1 Switch box fixing plate 6.28 Insulation switch box 6.
Disassembly and Maintenance 1 1.9 ESIEN05-04 FDEQ71, 100B Exploded view The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 10 Discharge plate assy 2 Suction plate assy 11 Bottom assy 3 Air filter 12 Filter holding plate 4 Fan assy 13 Hook 4.1 Fan top plate assy 14 Pipe support plate 4.2 Fan housing bottom (large) 15 Pipe sealing 4.3 Fan housing top (large) 16 Switch box assy 4.4.1 Rotor assy 16.1 Switch box cover assy 4.
Disassembly and Maintenance 1 1.10 ESIEN05-04 FDEQ125B Exploded view The illustration below shows the exploded view.
ESIEN05-04 Components Disassembly and Maintenance 1 The table below contains the components of the exploded view. No. Component No. Component 1 Top plate assy 7.5 Flare nut 5/8 2 Suction plate assy 8 Drain pan sealing assy 3 Air filter 9 Drain pan fixing 4 Fan assy 10 Discharge plate assy 4.1 Fan top plate assy 11 Bottom assy 4.2 Fan housing bottom (small) 12 Filter holding plate 4.3 Fan housing top (small) 13 Hook 4.4.1 Rotor assy 14 Pipe support plate 4.4.
Disassembly and Maintenance 1 1.
ESIEN05-04 Disassembly and Maintenance 1.11.1 Removal of Suction Grille Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Removing the suction grille 1 Points cPush the buttons and pull down Push the 2 buttons simultaneously and pul the suction grille down slowly. Q When closing, push up the grille slowly. 3 2 With the suction grille open at an angle of 45°, lift it up to remove it.
Disassembly and Maintenance 1 ESIEN05-04 1.11.2 Removal of Air Filter Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 3 Procedure Points Removing the air filter 1 Open the suction grille. (Refer to the procedure for removing the suction grille.) 2 Disengage the hooks of the air filter by pulling the filter downward at an angle, and remove the filter.
ESIEN05-04 Step 2 Disassembly and Maintenance Procedure Points 1 Mounting the air filter 1 2 Hook the air filter on projections at the top of Force the bottom of the air filter into projections at the bottom of the suction grille to secure the air filter.
Disassembly and Maintenance 1 ESIEN05-04 1.11.3 Removal of Decoration Panel Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 3 Procedure Points Removing the decoration covers in the corner of decoration panel 1 To remove the decoration covers in the corner, pull the inside (suction grille side) down.
ESIEN05-04 Disassembly and Maintenance Step 5 Procedure Remove the 2 mounting fixtures on the outside (Section A), then remove the 2 mounting fixtures on the inside (Section B). Points 1 Decoration panel String Mounting fixture Mounting fixture Mounting fixture 3 6 Remove the decoration panel. Q Mounting the decoration coverin the corner Mount the decoration cover so that 4 hooks on the decoration cover can engage with the hole in the decoration panel.
Disassembly and Maintenance 1 ESIEN05-04 1.11.4 Removal of Horizontal Blade Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Remove 4 screws each (16 screws in total) to dismount the 4 seal materials. 3 Seal material 2 55 Remove 2 screws each (16 screws in total) to dismount the 8 horizontal blade bearings.
ESIEN05-04 Disassembly and Maintenance 1.11.5 Removal of Swing Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step 1 Points Remove the decoration cover in the corner located right below the refrigerant piping. 3 Decoration cover in the corner 2 Remove the 2 swing motor mounting screws. 55 3 Disconnect the swing motor connector. Q The connector section is protected with the use of aluminum tape.
Disassembly and Maintenance 1 ESIEN05-04 Procedure Step Q Caution during swing motor installation 1. After installing the swing motor, be sure to turn off the power supply for reset (for initializing the vane positions). Q Points Protect the connector section with using the aluminum tape. Motor-side gear Swing motor 3 Panel-side gear 2 Be sure to engage the gears on the motor side and panel side. (Improper gear engagement results in faulty swing operation and abnormal noise.
ESIEN05-04 Disassembly and Maintenance 1.11.6 Removal of Switch Box Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step 1 2 Points Remove the 2 mounting screws on the switch box cover. Remove the 1 mounting screw on the terminal block cover. 3 Terminal block box cover Switch box cover 3 55 Disconnect each connector (7 connectors in total) connected to the inside of the switch box.
Disassembly and Maintenance 1 Procedure Step 4 5 6 ESIEN05-04 Disconnect the connector for fan motor. Q For FCQ71D : Direct connector Q For FCQ100~ 140D: Relay connector Points Fan motor Grounding wire Remove the grounding wire mounting screw. Remove the switch box fixing screw. 3 Switch box fixing screw 7 Tilt the switch box in the direction shown by the arrow, then draw the entire switch box out.
ESIEN05-04 Disassembly and Maintenance 1.11.7 Removal of PC Board Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step Q 1 1 Points Remove the switch box according to the procedure for removing the switch box. Remove 2 switch box mounting screws to open the box. 3 Disconnect the control PC board.
Disassembly and Maintenance 1 Procedure Step 3 ESIEN05-04 Points Disconnect the power supply PC board. 1 3 Disengage the 3 tabs on the front by pressing the back of the PC board in the direction shown by the arrow, then remove the power supply PC board.
ESIEN05-04 Disassembly and Maintenance 1.11.8 Removal of Humidity Sensor and Air Temperature Thermistor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step Q 1 2 Points Remove the terminal block box cover according to the procedure for removing the switch box. Disconnect the connector for humidity sensor. Disengage the 3 tabs to remove the humidity sensor.
Disassembly and Maintenance 1 ESIEN05-04 1.11.8 Removal of Fan Motor Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step Q 3 Points Remove the terminal block box cover according to the procedure for removing the switch box, then disconnect the following connectors.
ESIEN05-04 Procedure Step 2 1 Disassembly and Maintenance Points 1 Removing the fan rotor. Remove the resin nut and fan rotor retainer to dismount the fan rotor. 3 Fan rotor retainer Resin nut 3 1 2 Remove the fan motor. Disconnect the 2 connectors on the fan motor. Remove the nut with collar and vibro-isolating runner to dismount the fan motor.
Disassembly and Maintenance 1 ESIEN05-04 1.11.10 Removal of Drain Pan, Drain Pump, Float Switch Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 1 2 3 Procedure Points Removing the drain pan Remove the drain socket cap to discharge water. Remove the 5 mounting screws to pull the drain pan out downward.
ESIEN05-04 Procedure Step 2 Disassembly and Maintenance Points 1 Removing the drain pump 1 2 3 4 5 Cut the clamp material. Pull the drain hose out. Remove the 3 screws on the drain pump mounting plate. Remove the 2 mounting screws on the drain pump. Displace the drain pump sideward to remove it. When removing the drain pump, cut the following clamp materials. z Clamp material securing the drain pump lead wire to the drain pump mounting plate.
Disassembly and Maintenance 1 3 Step [Installation procedure of drain pump or float switch] 1 Install a spare drain pump or float switch on the mounting plate, then firmly secure the lead wires using the provided clamp materials (3 pieces). 2 Connect the lead wires of the drain pump or float switch in the original state, firmly secure the aforementioned clamp materials (screw type fixing) to the drain pan with the use of mounting screws.
ESIEN05-04 Disassembly and Maintenance 1.11.11 Removal of Heat Exchanger Temperature Thermistor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q 1 2 Remove the drain pan according to the procedure for removing the drain pan. Cut the clamp material. Draw the heat exchange temperature thermistor together with the insulation material out in the direction shown by the arrow.
Disassembly and Maintenance 1 1.
ESIEN05-04 Disassembly and Maintenance 1.12.1 Removal of Suction Grille Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing the suction grille 1 To remove the suction grille, slide the two tabs simultaneously and pull the suction grille down slowly. Q 3 The grille can be installed freely in four directions. Q When closing, push up the grille slowly.
Disassembly and Maintenance 1 ESIEN05-04 1.12.2 Removal of Air Filter Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing the air filter 1 Open the suction grille. (See "Removal of Suction Grille".) 3 (S2632) 55 2 Disengage the hooks of the air filter by pulling the filter downward at an angle, and remove the filter.
ESIEN05-04 Step 2 Disassembly and Maintenance Procedure Points 1 Installation of the air filter 1 Hook the air filter to the protrusions located at the top of the suction grille. 2 Push the lower section of the air filter into the protrusions located at the bottom of the suction grille to secure the air filter in place.
Disassembly and Maintenance 1 ESIEN05-04 1.12.3 Removal of Decoration Panel Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 3 Procedure Points Removing the decoration panel 1 Remove the switch box cover and disconnect the connector of swing motor from the harness connector of electric parts. (S2636) (S2637) 2 55 Check that the provisional hanger is in the position where it can be engaged with the hook of switch box.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure The decoration panel is attached with 4 mounting screws. Points 1 Loosen the two screws by approx. 10 mm Provisional hanger Remove the two fixing screws at the switch box side first. 4 Loosen the other two screws by approx. 10 mm. The decoration panel is hung with these two fixing screws and the provisional hanger.
Disassembly and Maintenance 1 Step 5 ESIEN05-04 Procedure Points Turn the provisional hanger to disengage it from the hook of switch box, and slide the decoration panel in the arrow direction to remove the panel.
ESIEN05-04 Disassembly and Maintenance 1.12.4 Removal of Horizontal Vane Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Q 2 Points Removing the decoration panel Refer to the "Removal of Decoration Panel" Remove the padding at four corners of frame fixed with three screws each. At that time, peel the end of black sealing material of discharge port in part.
Disassembly and Maintenance 1 Step 3 ESIEN05-04 Procedure Remove the two screws for each bearing of horizontal vane (16 screws in total). Points Fixing screws Fixing screws 3 (S2645) 4 Remove the horizontal vane.
ESIEN05-04 Disassembly and Maintenance 1.12.5 Removal of Swing Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Removing the decoration panel Points Fixing screw Refer to the "Removal of Decoration Panel" Pull out the swing motor harness from the wiring groove. Remove two mounting screws for swing motor mounting plate to remove the plate.
Disassembly and Maintenance 1 Step Q Procedure Points Precaution during swing motor insttallation 1 Engage the swing motor-side gear with the panel-side one. (Otherwise, faulty swinging operation or abnormal noise may be caused.) 3 ESIEN05-04 2 3 Install the motor after checking of correct gear engagement. Install the swing motor in reverse process of removal procedure. After installing the swing motor, be sure to turn on the power switch for resetting (for initializing the vane positions).
ESIEN05-04 Disassembly and Maintenance 1.12.6 Removal of Switch Box Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure Points Remove decoration panel first. 1 Fixing screw (M4×12) Remove the lid of switch box. (Two pieces of M4 screws) 3 Fixing screw (M5×12) Capacitor for fan (S2650) 2 Disconnect the connection wires for outdoor units and earth wire. At this time, cut the tie wrap fixing the connection wires.
Disassembly and Maintenance 1 Step 3 55 Procedure Remove five pieces of lead wires from PCB on the switch box and lead wire connected to the capacitor for fan motor. (Refer to the list shown in the right.) 4 Cut tie wraps fixing lead wires of float switch, thermistor for heating and liquid pipe thermistor. 5 Remove two fixing screws located at both ends of switch box and one screw inside the box. 6 Remove the switch box.
ESIEN05-04 Disassembly and Maintenance 1.12.7 Removal of Fan Rotor and Fan Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure Q Remove the switch box. Q Remove the bell mouth (Two screws) Points Q A convex protrusion is provided at the position of bell mouth fixing screw to prevent misjudgment with switch box fixing position.
Disassembly and Maintenance 1 Step 4 ESIEN05-04 Procedure Points Make sure to hold the hub as shown in Fig.1 when tightening or loosening the fan fixing nut with a spanner.To avoid deformation and vibration of the fan, do not apply excessive torque to the shroud (the slash part of Fig.2). Note: There is no problem to hold the shroud when carrying or lifting the fan. 3 Hub Fig. 1 Fan fixing method Shroud Fig.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Pull down the fan motor slowly.
Disassembly and Maintenance 1 ESIEN05-04 1.12.8 Removal of Drain Pan Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 3 Procedure 1 Remove the drain socket to drain water from the drain hole. 2 Remove the 4 mounting screws to remove the drain pan. Points Remove the drain socket to drain water from the drain hole. Q If water is in the drain pan, it can spill and wet the floor.
ESIEN05-04 Disassembly and Maintenance 1.12.9 Removal of Drain Pump Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing the drain pump 1 Remove two screws fixing float switch ass'y. (Screwdande) Screw 3 Screw Screw (S2660) 2 Remove the float switch ass'y. Q Remove the float switch before removing drain pump in order to prevent the float switch from damage.
Disassembly and Maintenance 1 Step 3 ESIEN05-04 Procedure Points Cut the tie wrap fixing the drain hose. Q Remove the screw c When pulling out the drain hose, be sure to wear safety gloves to prevent your finger from injury with heat exchanger fin. Screw 3 (S2662) 4 Pull out the drain hose. 5 Remove the drain pump.
ESIEN05-04 Disassembly and Maintenance 1.12.10 Installation of Drain Pump Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Installing the drain pump 1 Put the lead wire in the wiring groove properly, fix the drain pump ass'y with screw c and insert the drain hose.
Disassembly and Maintenance 1 Step 2 ESIEN05-04 Procedure Points Insert the drain hose into the hose plug of the drain pump up to the root of plug securely. Q Inserting the drain hose should be executed before installation of float switch in order to prevent the float switch from damage. Q Put the tie wrap on the white line on the hose inserted. White line 3 (S2666) (S2667) 3 55 Put the tie wrap on the hose.
ESIEN05-04 Step 4 Disassembly and Maintenance Procedure Points 1 Insert the float switch ass'y. At this time, put the lead wires in the wiring groove properly. 3 (S2661) 5 Install the drain pump together with the float switch with screw d and e. 55 When install the drain pan, put the lead wires of float switch and drain pump in wiring groove and pass the lead wires above on the black sealing material on the drain pan. (Otherwise, due dripping may occur due to leakage of cool air.
Disassembly and Maintenance 1 ESIEN05-04 1.12.11 Replacement of Heat Exchanger Thermistor Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Disconnect the grounding terminal from the header. 3 (S2670) 2 Pull apart the thermistor ass'y and motor lead wire from the clamps. Thermistor ass'y Fan motor lead wire Clamp Clamps 55 3 Pull out the thermistor from the slit of heat exchanger partition plate.
ESIEN05-04 Step 5 Disassembly and Maintenance Procedure Take out the two tie wraps fixing the anti sweat tube of header and thermistor. Points Q Anti sweat tube (Be sure not to take out other tie wrap.) Heat resistance tie wrap is used. Be sure to use a heat resistance tie wrap when installing new thermistor. 1 ∗ Heat resistance tie wrap Parts No. :1278921 (Drg No. :4SA90202-1) (S2673) 3 6 Pull out the thermistor from the insertion pipe.
Disassembly and Maintenance 1 ESIEN05-04 1.12.12 Replacement of Heat Exchanger Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 3 Procedure Points Removing the heat exchanger 1 Remove the refrigerant pipe after completion of refrigerant collection and pump down operation. 2 Q This work should be performed with two personnel including one person for supporting the heat exchanger to avoid falling down during the work.
ESIEN05-04 Disassembly and Maintenance Step 4 Procedure Points 1 Remove the heat exchanger. 3 (S2677) 2 Installing the heat exchanger 1 Insert the heat exchanger in the groove of ceiling polystyrene foam properly, and bring the tube plate section of heat exchanger into intimate contact with the polystyrene partition plate correctly. Groove of ceiling polystyrene foam.
Disassembly and Maintenance 1 Step Procedure 3 Install the heat exchanger mounting plate. 4 Insert two thermistors. Then cover the header by anti sweat tube. 3 ESIEN05-04 Points Q Heat exchanger mounting plate Set the lead wire with yellow tape (for heating) upper side while that with no tape (for liquid) lower side. (S2681) 55 Anti sweat tube (S2682) 5 Reinstall the lead wire of thermistor and anti sweat tube on the original position by using two pieces of heat resistance tie wrap.
ESIEN05-04 Disassembly and Maintenance Step 6 Procedure Put the heat exchanger partition plate inside and fix them with two screws. Points 1 Fan motor lead wire Heat exchanger partition plate (S2672) 3 Fan motor lead wire 7 Pass the thermistor ass'y through the clamps and the slit of partition plate securely as the original state. Clamp Clamps Pass the lead wire of motor also through the clamp securely.
Disassembly and Maintenance 1 3 Step 9 10 ESIEN05-04 Procedure Points Install the drain pan putting the lead wire of float switch and drain pump into the wire groove securely. When install the drain pan, put the lead wires in wiring groove and pass the lead wires above the black sealing material on the drain pan securely. (Otherwise, due dripping may occur due to leakage of cool air.) Installing the bell mouth.
ESIEN05-04 Step 12 Disassembly and Maintenance Procedure Points Install the switch box with two M4 screws and one M5 screw. Q For installation of the switch box, refer to the "Removal of Switch Box" on page 5-53. Q For re-wiring inside the switch box, refer to the "Replacement of PC Board" on page 5-72.
Disassembly and Maintenance 1 ESIEN05-04 1.12.13 Replacement of PC Board Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 1 3 Procedure Points Removing the PC Board 2 Remove the switch box cover. (M4 screw×2) Disconnect the connectors shown in the right connected to the PC board. Cut the tie wrap fixing the low tension cable (blue) to the switch box.
ESIEN05-04 Disassembly and Maintenance Step 2 Procedure Installing the PC board and re-wiring inside the switch box 1 Engage the PC board with two claws shown in the right figure, push up the board until a click sound is generated, then connect the lead wires shown right. 2 Next connect the lead wires in the route shown below and fix them with tie wrap in the following order.
Disassembly and Maintenance 1 ESIEN05-04 Step 3 Procedure Re-connect the outdoor unit connection wire, the earth wire and wire of remote control as they were, and fix them securely with tie wrap. Points Q Be sure to fix the lead wire to be connected to the connector X10A for low-tension cable of transformer to the switch box with tie wrap j. (The tie wrap is used for preventing the wire from contact with a hot part on the PC board.
ESIEN05-04 Step Disassembly and Maintenance Procedure 2 Insert the lead wires of swing flap to the connector on the PC board. 3 Install the cover of switch box and the grille.
Disassembly and Maintenance 1 ESIEN05-04 1.12.14 Replacement of Receiver Section of infrared remote control Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing the receiver section 1 Remove two screws of the transmission parts box to remove the box. Transmission parts box 3 X24 (S2694) 55 2 3 Cut the tie wrap fixing transmission parts box and harness and disconnect the connector X1A.
ESIEN05-04 Disassembly and Maintenance Step 4 Procedure Removing the decoration panel Points 1 Lead wire of receiver section Refer to "Removal of Decoration Panel" Pull out the lead wire of receiver section from wiring groove. Q 5 Push three claws to remove the corner cover. 6 Push three claws on the rear side of panel to remove the corner cover (receiver section).
Disassembly and Maintenance 1 Step ESIEN05-04 Procedure 3 Install the switch box and the decoration panel. 4 Insert the lead wire of the receiver section to connector X1A, and bind the two wires with tie wrap. 5 Set the dip switches. 6 Mount the transmission parts box with two screws after checking that the tie wrap is in the fixing position and the lead wire is caught with fixing part of tie wrap and can not come out.
ESIEN05-04 1.
Disassembly and Maintenance 1 ESIEN05-04 1.13.1 Removal of Air Filter and Suction Grille Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure 1 Push the 2 tabs and open the suction grilles. 2 Push the air filter installation panel from 2 places in the direction of the arrow, and pull the air filter out toward yourself.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Grip the suction grille hinge strongly and remove the suction grille.
Disassembly and Maintenance 1 ESIEN05-04 1.13.2 Removal of Electrical Parts and PC Boards Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure:. Step Procedure 1 Loosen the 2 screws of the control box cover and remove the control box cover. 2 Remove the 2 screws of the control box.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Pull down the control box and let it hang by the 2 locations in the rear. Electrical parts can now be removed. 3 4 Disconnect the connector mounted on the PC board. 55 5 Remove the PC board installation screw.
Disassembly and Maintenance 1 Step 6 ESIEN05-04 Procedure Points Slide the PC board to the left away from the tabs on the right, and remove the PC board.
ESIEN05-04 Disassembly and Maintenance 1.13.3 Removal of Horizontal Blade Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Gently bend the support plate located at the center of the horizontal blade, and detach the center shaft. (Two shafts provided on Types 140 and 160.) 2 Then gently bend the center of the horizontal blade, and take both the end shafts out of their bearings.
Disassembly and Maintenance 1 ESIEN05-04 1.13.4 Removal of Fan Rotor and Fan Motor Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Push the 2 tabs of the fan housing toward the inside with your fingers, and pull out the fan housing.
ESIEN05-04 Step 2 Disassembly and Maintenance Procedure Points 1 Loosen the 2 hexagon set screws of the intermediate bearing. 3 3 Slide the intermediate bearing to the right and remove the fan rotor ass’y.
Disassembly and Maintenance 1 Step 4 5 6 ESIEN05-04 Procedure Points Cut off the tie-wrap of the glass tube cover over the fan motor connector. Slide the glass tube and get the connector exposed. Disconnect the 2 fan motor connecting connectors. Remove the 2 fan motor fasteners. Q Aconnectors Connector (1) handles high voltage (220-240 V), so be sure to turn of the power supply before disconnecting. Remove the fan motor.
ESIEN05-04 Disassembly and Maintenance 1.13.5 Removal of Fan Bearing Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Points Remove the fan rotor according to the procedures for removing the fan rotor and fan motor. 1 Remove the left side panel installation screw.
Disassembly and Maintenance 1 Step 2 3 Procedure ESIEN05-04 Points Slide the left side panel toward the front of the unit and remove. Remove the 2 bearing installation screws and remove the bearing.
ESIEN05-04 Disassembly and Maintenance 1.13.6 Removal of Bottom Panel and Drain Pan Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Remove the 7 bottom panel installation screws (2 each on the left and right, 3 in the rear), and remove the bottom panel. Remove the rear surface screws (2 each on the left and right), and remove the center screw while supporting the bottom panel from underneath.
Disassembly and Maintenance 1 3 ESIEN05-04 Remove the drain pan retainer (2 screw).
ESIEN05-04 Disassembly and Maintenance 1.13.7 Removal of Swing Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 2 3 Procedure Points Remove the screw from the right side panel. Slide the right side panel toward the front and detach it. Cut off the tie-wrap of the swing motor connector. 3 Disconnect the connector from the swing motor connector. 55 4 Remove the screw from the swing motor.
Disassembly and Maintenance 1 1.
ESIEN05-04 Disassembly and Maintenance 1.14.1 Removal of Air Filter Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Opening suction grille Push two tabs on suction grille toward the center of grille at the same time. 3 2 Pull down suction grille. (Two strings are equipped to prevent the grille from dropping.) 55 3 To remove air filter, lift the tabs up at the same time and pull it forward.
Disassembly and Maintenance 1 ESIEN05-04 1.14.2 Removal of Suction Grille Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure 1 Unhook two drop-prevention strings while supporting suction grille with hand. 2 Open suction grille forward for approx. 45 degree.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Disengage three hooks located at rear side of the grille to remove suction grille.
Disassembly and Maintenance 1 ESIEN05-04 1.14.3 Removal of Fan Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure 1 Remove two mounting screws to dismount switch box cover. 2 Remove suction air temperature thermistor attached to bell mouth. Points 3 Edge of rib 55 Stick filament tape Edge of clamp (S1271) 3 Bell mouth is mounted with tree screws.
ESIEN05-04 Step 4 Disassembly and Maintenance Procedure Points 1 Remove bell mouth by sliding to piping direction. 3 5 To dismount fan, remove washer based nut using double-ended wrench. 55 6 Remove fan by pulling down.
Disassembly and Maintenance 1 ESIEN05-04 1.14.4 Removal of Fan Motor Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing fan motor a. Disconnect connector. b. Remove lead wire retaining plate. 3 Caution: Fan motor can be removed without removing the lead wire retaining plate. However, when washing the heat exchanger, this plate should be removed and protect the lead wires.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Remove motor by pulling down.
Disassembly and Maintenance 1 ESIEN05-04 1.14.5 Removal of Drain Pan Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step Q Points Remove suction grille according to the Removal of air filter and that of suction grille. 3 55 1 2 5–102 To dismount three corner sections A, B and C, remove a flocked screw. Remove three flocked screws to dismount corner section D.
ESIEN05-04 Procedure Step 3 Disassembly and Maintenance Points 1 Disconnect wires and connectors from PCB. 3 4 Arrange wire harness to avoid interference with next process. Caution: This work should be done by two personnel. If drain water remain in the pan, it may drop and stain on the floor. Make sure to check if no drain water remain in the pan, or cover the floor with vinyl sheet before disassembling work.
Disassembly and Maintenance 1 Procedure Step 6 ESIEN05-04 Points Remove drain pan by pulling it down.
ESIEN05-04 Disassembly and Maintenance 1.14.6 Removal of Drain Pump Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Drain pump is located at piping side. Cut clamp material of hose, and disconnect hose from pump. 2 Points Caution: When reconnect drain hose with the pump, secure hose at joint using clamping material such as Tielap. (Clamping material should be normally included in the stock items.
Disassembly and Maintenance 1 Step 4 ESIEN05-04 Procedure Points Removing float switch a. Loosen three mounting screws to remove drain pump mounting base. b. Remove two screws located at opposite side of drain pump mounting base to dismount float switch.
ESIEN05-04 Disassembly and Maintenance 1.14.7 Removal of Swing Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Points Remove suction grille according to "Removal of Suction Grille" 1 Swing motor is located at the diagonal position of piping. 2 Remove two mounting screws for swing motor cover. 3 Remove swing motor cover by holding two tabs on the cover.
Disassembly and Maintenance 1 Step 4 ESIEN05-04 Procedure Points Remove two screws to dismount swing motor.
ESIEN05-04 Disassembly and Maintenance 1.14.8 Removal of Air Flow Control Blade Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points To remove horizontal blade, press down tabs located at both end of blade and pull them forward.
Disassembly and Maintenance 1 Step 2 ESIEN05-04 Procedure Points Remove horizontal blade.
ESIEN05-04 1.
Disassembly and Maintenance 1 ESIEN05-04 1.15.1 Removal of Air Filter and Front Panel Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure 1 Put your fingers on protrusions at left and right side of the unit to open the front panel. 2 To remove the air filter, push up the tab and pull down the filter. Points 3 55 5–112 Q The air filter is free from the side of left or right.
ESIEN05-04 Step 3 Disassembly and Maintenance Procedure Points 1 Disengage the holding section on upper right of the panel by pushing toward left, then slide toward right to remove the front panel.
Disassembly and Maintenance 1 ESIEN05-04 1.15.2 Removal of Front Grille Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Points Removing the front panel in accordance with "Removal of Front Panel". 1 Remove three pieces of front grille fixing screws. 3 2 Remove the front grille by pulling forward while pushing three hooks located at upper part of the grille one by one.
ESIEN05-04 Disassembly and Maintenance 1.15.3 Removal of the horizontal blade and vertical blade Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step 1 Procedure Points Removing the horizontal blade. 1 Open the horizontal blade. 2 Bend the horizontal blade slightly to disengage the fixing part at right side. 3 Pull the horizontal blade rightward and take it out.
Disassembly and Maintenance 1 Step 2 ESIEN05-04 Procedure Removing the vertical blade. 1 Disengage the protrusion on upper side of blade from holder plate. (Three locations) 2 Push the vertical blade backward and pull the lower side forward to disengage the blade from three hooks.
ESIEN05-04 Disassembly and Maintenance 1.15.4 Removal of Electrical Box Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Points Removing the front grille in accordance with "Removal of Front Grille". 1 Remove the screw on the service cover. 2 Remove the screw on the drip proof plate. 3 Remove the screw for the grounding wire. 4 3 Remove the following connectors.
Disassembly and Maintenance 1 ESIEN05-04 1.15.5 Removal of Heat Exchanger Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q 3 Procedure Removing the front grille in accordance with "Removal of Front Grille". Removing the switch box in accordance with "Removal of Electrical Box". 1 Press strongly the claws on both left and right sides of heat exchanger toward inside.
ESIEN05-04 Disassembly and Maintenance 1.15.6 Removal of Fan Motor and Fan Rotor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure Points Removing the front grille in accordance with "Removal of Front Grille". Removing the electrical box in accordance with "Removal of Electrical Box".
Disassembly and Maintenance 1 ESIEN05-04 1.15.7 Removal of Air Swing Motor Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q 3 Procedure Points Removing the front grille in accordance with "Removal of Front Grille". 1 Disconnect the air swing motor connector in the electrical box. 2 Remove the screw which fixes the air swing motor. 55 3 5–120 Pull the air swing link assembly to the left strongly to dismantle.
ESIEN05-04 Disassembly and Maintenance 1.15.8 Drain Hose Piping to the Left Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Removing the front grille in accordance with "Removal of Front Grille". 1 Pull out the drain hose attached on the rear right of the unit. Points Q The drain pan and bottom frame are designed as an integral-type.
Disassembly and Maintenance 1 1.
ESIEN05-04 Disassembly and Maintenance 1.16.1 Removal of Air Filter Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure Points 3 1 Hold the air filter tabs with your hands and pull out. 2 Pull the air filter out.
Disassembly and Maintenance 1 ESIEN05-04 1.16.2 Removal of Slide Panel, Operation Display Cover, and Front Grille Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Procedure 1 Remove the left and right side panels. (1 white screw each on left and right) 2 Remove the operation display cover installation screw and remove the cover by sliding to the right.
ESIEN05-04 Disassembly and Maintenance 1.16.3 Removal of Electrical Parts Box Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Remove the left and right side panels, operation display cover and front grille according to the procedures for their removal. 1 2 3 Points The left and right side panels have to be taken off in order to remove the front grille.
Disassembly and Maintenance 1 ESIEN05-04 1.16.4 Removal of PC Board Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step Points Remove the outer panels according to the procedure for "Removal of Electrical Parts Box". 1 Disconnect the front side wiring connector connected to the PC board. Q 3 2 55 Disconnect the PC board from the tabs by pushing it inward.
ESIEN05-04 Disassembly and Maintenance 1.16.5 Removal of Swing Louvre Unit Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Points Remove the electrical parts box according to "Removal of Electrical Parts Box". 1 Remove the horizontal blade. 3 2 Remove the swing Louvre unit.
Disassembly and Maintenance 1 Step 3 ESIEN05-04 Procedure Remove the swing motor from the swing Louvre unit. Points You can replace the swing motor without removing the swing Louvre unit.
ESIEN05-04 Disassembly and Maintenance 1.16.6 Removal of Fan Motor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Remove side panels and other external casing, and electrical parts box according to their removal procedures. 1 Loosen the hexagon set screw fastening the fan rotor and fan motor. 2 3 Points Use 2.5 mm hexagon nut driver. 3 Remove the fan motor fastener. (3 screws) 55 Remove the fan motor.
Disassembly and Maintenance 1 ESIEN05-04 1.16.7 Removal of Drain Pan Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Procedure Step If removing the drain pan: Carry out pump down, disconnect the transmission piping and wiring, and remove the main unit. Q Remove side panels, operation display cover and front cover according to their removal procedures. 1 Remove the bottom panel.
ESIEN05-04 Procedure Step 3 Disassembly and Maintenance Remove the air discharge unit. (7 screws) Points Center of air discharge section also screw fastened. 1 3 4 Remove the drain pan. 1 Pull left side toward yourself. 2 Move the drain hose to the right until it comes off.
Disassembly and Maintenance 1 ESIEN05-04 1.16.8 Removal of Heat Exchanger Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q 3 Procedure Before dismounting a heat exchanger, make sure to proceed pump down refrigerant to outdoor unit and disconnect the connection pipe and wiring, then remove the indoor unit.
ESIEN05-04 Disassembly and Maintenance 1.16.9 Removal of Fan Rotor Warning 1 Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Procedure: Step Q Procedure Remove the heat exchanger according to "Removal of Heat Exchanger". 1 Remove the 2 screws of the left side panel. Points You can also remove the auxiliary electric heater without removing the heat exchanger. 3 2 55 Remove the fan rotor by sliding to the left and pulling out toward yourself.
Disassembly and Maintenance ESIEN05-04 1 3 55 5–134 Part 5 – Disassembly and Maintenance
ESIEN05-04 Index 1 Symbols "88" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3–17 3 A A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 3–32 A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ESIEN05-04 1 Control Condensation avoidance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 2–19, 2–20, Draft avoidance control 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k Draft avoidance control 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k Drain pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ESIEN05-04 1 FCQ71~140D Removal of Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–24 Removal of Decoration Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–26 Removal of Drain Pan, Drain Pump, Float Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–38 Removal of Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ESIEN05-04 1 L Locating Exploded views, indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5–3 Functional diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–55 PCB layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1–107 Switch box layout. . . . . . . . . . . . . . . . . . .
ESIEN05-04 1 S Safety devices Indoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–30 Self-Diagnosis by Wired remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3–21 Setting Address for receiver of infrared remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4–5 Address for infrared remote control. . . . . .
ESIEN05-04 1 W Wiring diagrams Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Daikin units comply with the European regulations that guarantee the safety of the product.