Specifications

26
Slim Ceiling Mounted Duct Type (700 mm width type)
Galvanised steel plate
7,800
2,000
9,900
2,500
12,600
3,200
2.2
0.086 0.086 0.089
8.0/7.2/6.4
282/254/226
8.0/7.2/6.4
282/254/226
8.0/7.2/6.4
282/254/226
33/31/29 33/31/29 33/31/29
Airflow rate (HH/H/L)
m
3
/min
cfm
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
200
X
700
X
620
23.0
6.4
12.7
200
X
700
X
620
23.0
6.4
12.7
200
X
700
X
620
23.0
6.4
12.7
2.8 3.6
2.3 2.9 3.7
VP20 (External Dia, 26/Internal Dia, 20)
30-10
1
FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
MODEL
without
drain pump
FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
with
drain pump
Power consumption
(FXDQ-PBVE)
kW
0.067 0.067 0.070
Power consumption
(FXDQ-PBVET)
kW
0.160 0.165 0.181
Power consumption
(FXDQ-NBVE)
kW
0.147 0.152 0.168
Power consumption
(FXDQ-NBVET)
kW
Power supply
Cooling capacity
kW
(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (H
X
W
X
D) mm
Machine weight kg
Piping
connections
Drain
Liquid (Flare)
Gas (Flare)
mm
dB(A)Sound level (HH/H/L)
PaExternal static pressure
3
2
Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
Galvanised steel plate
1-phase, 220-240 V/220 V, 50/60 Hz
VP20 (External Dia, 26/Internal Dia, 20)
44-15
1
16,000
4,000
19,800
5,000
24,900
6,300
10.5/9.5/8.5
371/335/300
12.5/11.0/10.0
441/388/353
16.5/14.5/13.0
583/512/459
34/32/30 35/33/31 36/34/32
200
X
900
X
620
27.0
6.4
12.7
200
X
900
X
620
28.0
6.4
12.7
200
X
1,100
X
620
31.0
9.5
15.9
4.5 5.6 7.1
4.7 5.8 7.3
FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Airflow rate (HH/H/L)
m
3
/min
cfm
Casing
MODEL
without
drain pump
with
drain pump
Power supply
Cooling capacity
kW
(*1)
(*2)
Btu/h(*1)
kcal/h(*1)
Dimensions (H
X
W
X
D) mm
Machine weight kg
Piping
connections
Drain
Liquid (Flare)
Gas (Flare)
mm
dB(A)Sound level (HH/H/L)
PaExternal static pressure
3
2
Note: Specifications are based on the following conditions;
Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting
is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: external static pressure of 10 Pa.
Equivalent piping length: 7.5 m •Level difference: 0 m
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.