User`s manual

3837
DIMENSIONS (Unit: mm) Installation service space for outdoor unit
Wired type
Staple
Remote
controller
17
17
0~5
117
Remote
controller
Remote
controller
(Between remote
controller and
control box)
17
• Installation method
A
Exposed body, exposed cord
C
Exposed body, embedded code
B
Exposed body, embedded cord
Conduit
Control box
Through hole
Size
Specifications of cord
0.75~1.25 mm
2
Total length
500 m
Type
Shield wire
(insulated thickness: 1 mm or more)
Note)
1. Remote controller cord and staple are not attached.
They are field supplied parts.
120
120
17
18
42
84
38
Cord
outlet
hole
2823
46
• Remote controller dimensions
REMOTE CONTROLLER
Wireless type
CEILING MOUNTED CASSETTE TYPE
Remote controller dimensions
Remote controller holder
installation procedure
<installation to wall surface>
• Receiver installation procedure
• Receiver detail
Transmitting part
157
62 17.5
Liquid crystal
remote controller
(wireless)
Remote controller
holder
WALL MOUNTED TYPE
• Receiver installation procedure
CEILING SUSPENDED TYPE
Receiver
• Receiver installation procedure
• Receiver
detail
The Front
• Receiver
detail
Receiver
120
72
83.5
106
(Ceiling opening)
70
18
0.5
35
49
Service space for ceiling installation
Receiver detail
Note :
More than 90
(Srevice space)
(Ceiling opening)
2
-
5
x
9 Slot
Switch box
(field Supplied parts)
Do not install more than 3 receivers in
the vicinity of one another.
With 4 or more units, there is always
the possibility of malfunction
( 12- 16)
Receiver
Drain piping
side
Refrigerant
piping side
Decoration panel
1000
or more
300(200)
or more
L
H
L H
H
L
500
or more
100(50)
or more
L H
For RZQ71-100FV4A, RZQ100-160KV4A
300(200) or more
1000 or more
200 or more
100 or more
100 or more
100 or more
100(50) or more
1000
or more
500
or more
When there is an obstruction on the inlet side
When the obstruction on the outlet side is higher than
the unit itself (There is no limit to the height of the
obstruction on the outlet side.)
When there are obstructions on both
the inlet and outlet sides
When there is an obstruction on the outlet side
When there are obstructions
on the inlet side and
both lateral sides
2. For series installation
(more than two units)
When there are
obstructions on
both sides
When the overhead space is open
1. For single unit installation
When there is an
obstruction only
on the inlet side
When there is an obstruction
in the overhead space
When the overhead space is open
When there are obstructions
on both sides
When there is an obstruction
in the overhead space
When there is an
obstruction on the
inlet side
When there are obstructions
on the inlet side and
both lateral sides
Pattern 1
2. For series installation (more than two units)
1. For single unit installation
1. For single unit installation
When the overhead space is open
2. For series installation
(more than two units)
1. For single unit installation
2. For series installation
(more than two units)
1. For single unit installation
2. For series installation
(more than two units)
100 or more
500 or less
1000
or more
An obstruction
in the overhead
space
500
or less
500
or more
1000
or more
An obstruction
in the overhead space
500
or less
1000
or more
1000
or more
An obstruction
in the overhead space
150 or more
150 or more
150 or more
500 or less
1000
or more
An obstruction
in the overhead
space
300(200)
or more
1000 or more
200 or more
500 or less
1000
or more
An obstruction
in the overhead
space
The values represent the case for the RZQ100-160KV4A.
The dimensions in ( ) are for the RZQ71-100FV4A (The unit values is mm. )