Service manual

Indoor Unit Functional Concept ESIE04-01
2–26 Part 2 – Functional Description
3
1
2
4
5
2.2 Thermostat Control
Purpose Based on the information received from the air return sensor, the thermostat control will decide the
required operation status of the system.
Thermostat control Cooling mode:
Heating mode:
Cool / heat changeover in automatic mode:
Preventing
thermostat OFF
conditions
The thermostat control prevents the thermostat from turning OFF in the following conditions:
P Initial operation for the first 2.5 minutes, or
P Defrosting, or
P Forced operating mode
Remark: The thermostat control will be changed when using field settings for low humidity applications, setting
16(26)-2-03 & 16(26)-2-04.
See "Part 4–Commissioning and Test Run" for details.
Thermostat OFF
–0.5 K
Set point
+1 K
Thermostat ON
Thermostat ON
–1 K
Set point
+0.5 K
Thermostat OFF
Automatic heating
–2 K
Set point
+2 K
Automatic cooling