Service manual
General Functionality ESIE04-01
2–10 Part 2 – Functional Description
3
1
2
4
5
1.6 Restart Standby
Outline To prevent the compressor from frequently turning ON and OFF and allow pressure equalization,
forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard
timer).
Graph
Thermostat OFF
Compressor
Electronic expansion valve
Oudoor unit fan
ON
ON
OFF
OFF
OFF
Restart standby
complete
Residual
operation
For 3 minutes
Moves to “Stop” or
“Starting control” after
completion of “Restart
standby”.
RZQ - Final.book Page 10 Monday, September 20, 2004 11:24 AM