Specifications

SiBE04-624 Control Specification
Function and Control 73
3.13 Automatic Defrosting
Defrost Control Start Condition
is calculated by the following formula:
= –17/256 × compressor operation frequency + 43/64 × outside air temperature – 6
However, when the calculated value is less than the lower limit indicated in the table below, the
lower limit is adopted as .
Operation during Defrosting and Termination Condition
Operation should be conducted at 64Hz during defrosting.
Defrosting operation must be conducted for 2 minutes, and after that, defrosting operation is
conducted until the outdoor heat exchanger temperature reaches the defrost cancellation
temperature at ºC.
After the temperature has reached the defrost cancellation temperature, the defrosting
should be terminated.
is calculated by the following formula:
= 18 – 22/64 × outside air temperature
However, when the calculated value is outside the range between 6ºC and 22ºC, if it is less than
6ºC, 6 should be adopted and if it is more than 22ºC, 22 is adopted, as the defrost cancellation
temperature.
Outside air temperature condition Lower limit
–4ºC outdoor air temp –15ºC
–10ºC outdoor air temp. < –4ºC –20ºC
outdoor air temp. < –10ºC –22ºC
Defrost control starts
and
or
Heating mode
and
Heating mode
Compressor is in operation
6 or more minutes passed since the
compressor started its operation
The cumulative time of heating operation
reached 25 minutes or more
The cumulative time of heating operation
reached 4 hours or more
Outdoor heat exchanger temperature
< 0ºC
The state that the outdoor heat exchanger
temperature < ºC has continued for 1
minute or more