Specifications
SiBE04-624 Control Specification
Function and Control 65
3.4 Compressor Start up Protection
Detail The gradual build-up of the upper operation frequency is illustrated in the graph below.
Fig. : Compressor protection function graph.
Timers and frequencies for the compressor protection function
RXR(28-50)
Cooling Heating
FCG1 52 48
FCG2 54 58
FCG3 78 80
FCG4 98 98
TCG1 220 220
TCG2 140 140
TCG3 60 60
TCG4 60 60
TCG1 TCG2 TCG3 TCG4
FCG4
Frequency
(Hz)
FCG3
FCG2
FCG1
(R5908)
Time
(sec)