Specifications

Main Functions SiBE04-624
20 Function and Control
Time chart for
humidifying
operation control
Approx. 1min. after heating operation start up, it repeats humidifying and drying alternately (to
protect condensation for inside the hose).
+
“Humidifying only operation” has no 1min-delay, it immediately starts up from
, and works
in the same sequence as others .
Time chart for “humidifying only test operation”
“Humidifying only test operation” on trial mode works in the same sequence as humidifying
operation, but about 30 min. later it automatically stops.
Remarks
1. When a room is spacious such as loft style or partitioned by accordion style curtain, the
ventilation volume is large and may not sometimes reach the set humidity.
2. When room temperature falls (12°C or lower), though “humidifying only test operation” is
functionally possible, humidifying heating operation continues to keep room temperature.
. Humidifying time Approx. 70min.
Decide time according to the outdoor temperature
and hose length set by remote controller.
. Drying time Approx. 2~10min.
Decide time according to the hose length set by
remote controller.
’. Drying time Approx. 2~10min.
Heating
operation
ON
OFF
Humidifying
fan damper
ON
OFF
Hygroscopic
fan
ON
OFF
Heater
ON
OFF
Rotor
ON
OFF
Approx. 1min
Approx. 3min
15 sec. 15 sec.
Dry mode
b' b'aaabb
(R5953)