Specifications

Check SiBE04-624
212 Service Diagnosis
3.14 Humidity Sensor Check
Check No.27 1. Check for proper connection.
2. Check sensor input level
(*1).
3. Change ambient conditions
(*2) and check that input level changes accordingly.
*1 Input level varies depending on the sensor.
*2 Changes in humidity, temperature, air flow rate. To do this, merely breathe upon.
3.15 Main Circuit Short Check
Check No.29
Measure the resistance between pins at both ends of DB1.
If the resistance is or less than 1 k, the main circuit short.
1
2
3
4
5
6
Buzzer
Humidity sensor
Room temperature thermistor
5V
<Humidity sensor>
S48
GND
12V
C70
(R6023)
(–) terminal of the tester
(in case of digital,
(+) terminal)
(~) (+) (~) (–)
(+) terminal of the tester
(in case of digital,
(–) terminal)
(+) (~) (–) (~)
Resistance in OK
several k
~several M
∞∞
several k
~several M
Resistance in NG 0 or
0 0 0 or