Specifications
Check SiBE04-624
208 Service Diagnosis
3.10 Discharge Pressure Check
Check No.16
Replace the compressor.
Set the stop valve open.
Replace the field piping.
Clean it.
Replace the compressor.
Discharge pressure check
Is it high?
YES
YES
NO
NO
NO
NO
Is the stop valve open?
Is the connecting
piping deformed?
Is the
heat exchange filter dirty?
YES
YES
(R3470)