Specifications

Check SiBE04-624
202 Service Diagnosis
3. Check
3.1 Thermistor Resistance Check
Check No.2 Remove the connectors of the thermistors on the PCB, and measure the resistance of each
thermistor using tester.
The relationship between normal temperature and resistance is shown in the graph and the
table below.
For the models in which the thermistor is directly mounted on the PCB.
Thermistor R25°C=20k B=3950
Temperature (°C)
–20 211.0 (k)
–15 150
–10 116.5
–5 88
0 67.2
5 51.9
10 40
15 31.8
20 25
25 20
30 16
35 13
40 10.6
45 8.7
50 7.2
RTH1
Tester
(R3460)