SiBE04-624 Troubleshooting
Service Diagnosis 173
2.24 High Pressure Control in Cooling
Remote
Controller Display
F6
Outdoor Unit LED
Display
A5 55 ( - )
Method of
Malfunction
Detection
During cooling, high pressure control (stop, frequency attenuation, etc.) is executed according
to the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
During cooling, when the temperature detected by the heat exchanger thermistor is 63°C or
more. (Fault condition is cleared when the temperature is below 52°C.)
Supposed
Causes
Insufficient installation space
Defective outdoor fan
Defective electronic expansion valve
Defective heat exchanger thermistor
Defective outdoor unit PCB
Defective stop valve
Defective solenoid valve for dehumidification