Specifications
Troubleshooting SiBE04-624
170 Service Diagnosis
2.22 Four Way Valve Fault
Remote
Controller Display
EA
Outdoor Unit LED
Display
A5 5 5 ( - )
Method of
Malfunction
Detection
The room temperature thermistor, the indoor heat exchanger thermistor, the outdoor air
thermistor, and the outdoor heat exchanger thermistor are checked to see if they function within
their normal ranges in the operating mode.
Malfunction
Decision
Conditions
When one of the follow condition continues for 10 min, the compressor stops, and restarts
automatically after 3 minutes standby.
Cooling / drying
(Room temperature – temperature of indoor heat exchanger) < – 5°C
Heating
(Temperature of indoor heat exchanger – room temperature ) < – 5°C
Shut down when the error repeats twice
Clear condition : Continuous operation for 60 minutes.
Supposed
Causes
Improper connector connection
Defective thermistor
Defective outdoor unit PCB
Defective coil or harness of 4-way valve
Defective 4-way valve
Insufficient gas
Foreign substance mixed in refrigerant