Specifications
Troubleshooting SiBE04-624
168 Service Diagnosis
2.21 Input Over Current Detection
Remote
Controller Display
E8
Outdoor Unit LED
Display
A5 5 5 ( - )
Method of
Malfunction
Detection
Detect an input overcurrent by checking the inverter power consumption or the input current
detected by CT with the compressor running.
Malfunction
Decision
Conditions
When 14 A or more of inverter power consumption or CT input continues for 5 sec.
The compressor stops if the error occurs, and restarts automatically after 3 minutes standby.
Supposed
Causes
Overcurrent due to defective compressor
Overcurrent due to defective power transistor
Overcurrent due to defective electrolytic capacitor of inverter main circuit
Overcurrent due to defective outdoor unit PCB
Detection error due to defective outdoor unit PCB
Overcurrent due to short circuit